Commissioning
When commissioning the ASD 533, it is necessary to perform an
initial reset to automatically adjusting the airflow monitoring on the
connected sampling pipe.
If the ASD 533 is operated without “ASD PipeFlow” calculation, the
commissioning can be carried out directly on the ASD 533 using
the “
EasyConfig
”
process
.
For projects in which the ASD PipeFlow calculation software was
used or in which customer-specific adjustments to the device con-
figuration are required, use the “
ASD Config
” configuration soft-
ware.
Startup
Before the ASD 533 is switched on, make sure all the
precautions required for its operation have been taken
(see also T 140 287, Sec. 7.1).
•
Sampling pipe correctly laid and connected;
•
Smoke sensor removed from protective packaging,
mounted and connected;
•
Isolation strip on the lithium battery (AMB 33) re-
moved.
Startup sequence and procedure:
1.
Switch on supply voltage (FACP); the next procedure can be
carried out while the fan is ramping up to its definitive speed
(takes about 100 s).
The system is immediately armed for
alarm
.
2. “
EasyConfig
”
: Select the required switch position for opera-
tion in accordance with the “
Table of system limits
” (e.g.
“
b21
”)
see also under “
Re-programming
”.
- or:
„
ASD Config
”: after making adjustments to the configuration
(alarm threshold acc. to ASD PipeFlow, other criteria acc. to
Tables A and B) select switch position “
X01
”, “
X02
” or “
X03
”.
3.
Set date and time via AMB 33 on “EasyConfig” or from
“ASD Config” (adopt settings from PC).
4.
After a
minimum waiting time of 5 min
after switch-on, carry
out an initial reset (possible only via AMB 33)
see also un-
der „
Initial reset
“.
5.
The ASD 533 is now ready for operation.
Re-programming
Example: Response grade B, system limit 2, switch position requi-
red
b21
.
Measure
Display
Procedure, remarks
Switch positions
W01
to
W44
are to be used only after
prior consultation with the manufacturer. The airflow
monitoring values stored under those switch positions are
not
tested in accordance with EN.
1.
Press the “UP”
key
flashing
C31
•
Displays the default
setting
2.
Press “UP” key
twice until dis-
play shows
b
in succession
A
/
b
•
Displays the switch
position group
b
3.
Press the “OK”
key
b11
•
Displays the smallest
possible position in
group
b
4.
Press the “UP”
key until dis-
play shows
b21
alternatively
b11
/
b21
•
Displays the possible
positions in group
b
5.
Press the “OK”
key
flashing
b - -
(approx. 4 x)
•
New setting is pro-
grammed
6.
Check: Press
the “UP” key
flashing
b21
•
Displays the new set-
ting
Initial reset
Measure
Display
Procedure, remarks
Before carrying out an initial reset – i.e. after switching on
the ASD 533 – make sure you observe a
waiting time of
at least 5 min
.
1.
Press the “UP”
key
flashing
C31
or
others
•
Displays the default
setting or the installa-
tion-specific switch
position
2.
Press the “UP”
key several
times until dis-
play shows
U
in succession
A
to
U
•
Displays the switch
position group
U
3.
Press the “OK”
key
U01
•
Displays initial reset
On
4.
Press the “OK”
key again
flashing
U - -
(5 to max. 120 s)
•
Initial reset in pro-
gress
5.
Wait
flashing point
(watchdog indica-
tor)
•
Initial reset com-
pleted
Filter replacement
When filter monitoring is activated and after expiry of the config-
ured filter service life, a “Filter fault (service life exceeded)” fault is
triggered. To remedy, the filter element in a filter-box or dust filter
unit must be replaced. When the expired filter service life (read out
via
EasyConfig
switch position
d
>
RE
) is periodically checked, the
replacement can take place before the fault is triggered.
For an activated filter replacement the ASD is set to the
“
isolate
” state. This insures that during the replacement
work falling dust particles from the filter element do not
cause a false alarm.
When the ASD 533 housing is closed, the “Start filter replacement”
function can be activated by means of the
“Reset” key
(provided
the filter monitoring is activated). To do so, press the key
longer
than 15 s
(attention: lamp test after 10 s). After 15 s the filter re-
placement is started and indicated by switching to the “Isolate”
state (Fault and LED “Fault”). When the “Reset” key is deactivated
(via ASD Config), the “Start filter replacement” function is not ac-
cessible.
After the filter has been replaced, the “Filter replacement” proce-
dure is completed by pressing the
“Reset” key
on the ASD. This
cancels the “Isolate” state and resets the fault on the ASD. “Filter
service life” monitoring is restarted at 0.
The filter replacement can also be started via
EasyConfig
switch
position
d
>
SE
. For information please refer to Technical Descrip-
tion T 140 287, Section 7.8.
Measurements / commissioning protocol
Carry out the following measurements:
•
Measure voltage at terminals 1 (+), 2 (-) (also terminals 3 and 4
in the case of a redundant voltage supply)
target value =
12.3 to 13.8 (in 12 VDC operation) and 21.6 to 27.6 VDC (in
24 VDC operation)
•
Airflow value in switch positions
V
(see also Technical descrip-
tion, T 140 287, Sec. 7.6.1).
The commissioning protocol is like a personal history of the
ASD 533 and should therefore be filled out conscientiously and
completely and stored in the ASD 533. If required, a copy can be
made and stored in the installation dossier.