Commissioning

When commissioning the ASD 533, it is necessary to perform an 

initial reset to automatically adjusting the airflow monitoring on the 

connected sampling pipe.
If the ASD 533 is operated without “ASD PipeFlow” calculation, the 

commissioning can be carried out directly on the ASD 533 using 

the “

EasyConfig

” 

process

For projects in which the ASD PipeFlow calculation software was 

used or in which customer-specific adjustments to the device con-

figuration are required, use the “

ASD Config

”  configuration soft-

ware.

Startup 

Before the ASD 533 is switched on, make sure all the 

precautions required for its operation have been taken 

(see also T 140 287, Sec. 7.1).

Sampling pipe correctly laid and connected;

Smoke sensor removed from protective packaging, 

mounted and connected;

Isolation strip on the lithium battery (AMB 33) re-

moved.

Startup sequence and procedure:

1.

Switch on supply voltage (FACP); the next procedure can be

carried out while the fan is ramping up to its definitive speed

(takes about 100 s). 

The system is immediately armed for

alarm

.

2. “

EasyConfig

: Select the required switch position for opera-

tion in accordance with the “

Table of system limits

”  (e.g.

b21

”)

see also under “

Re-programming

”.

- or:

ASD Config

”: after making adjustments to the configuration

(alarm threshold acc.  to ASD PipeFlow, other criteria acc.  to

Tables A and B) select switch position “

X01

”, “

X02

” or “

X03

”.

3.

Set date and time via AMB 33 on “EasyConfig” or from

“ASD Config” (adopt settings from PC).

4.

After a 

minimum waiting time of 5 min

after switch-on, carry

out an initial reset (possible only via AMB 33) 

  see also un-

der „

Initial reset

“.

5.

The ASD 533 is now ready for operation.

Re-programming

Example: Response grade B, system limit 2, switch position requi-

red 

b21

Measure

Display

Procedure, remarks

Switch positions 

W01

to 

W44

are to be used only after 

prior consultation with the manufacturer. The airflow 

monitoring values stored under those switch positions are 

not

tested in accordance with EN.

1.

Press the “UP”

key

flashing 

C31

Displays the default

setting

2.

Press  “UP” key 

twice until dis-

play shows 

b

in succession 

A

/

b

Displays the switch

position group 

b

3.

Press the “OK”

key

b11

Displays the smallest

possible position in

group 

b

4.

Press  the  “UP”

key until dis-

play shows 

b21

alternatively 

b11

/

b21

Displays the possible

positions in group 

b

5.

Press the “OK”

key

flashing 

b - -

(approx. 4 x)

New setting is pro-

grammed

6.

Check: Press 

the “UP” key

flashing 

b21

Displays the new set-

ting

Initial reset

Measure

Display

Procedure, remarks

Before carrying out an initial reset – i.e. after switching on 

the ASD 533 – make sure you observe a 

waiting time of 

at least 5 min

1.

Press the “UP”

key

flashing 

C31

or 

others

Displays the default

setting or the installa-

tion-specific switch 

position

2.

Press the “UP”

key several 

times until dis-

play shows 

U

in succession 

A

to 

U

Displays the switch

position group 

U

3.

Press the “OK”

key

U01

Displays initial reset

On

4.

Press the “OK”

key again

flashing 

U - -

(5 to max. 120 s)

Initial reset in pro-

gress

5.

Wait

flashing point 

(watchdog indica-

tor)

Initial reset com-

pleted

Filter replacement

When filter monitoring is activated and after expiry of the config-

ured filter service life, a “Filter fault (service life exceeded)” fault is 

triggered. To remedy, the filter element in a filter-box or dust filter 

unit must be replaced. When the expired filter service life (read out 

via 

EasyConfig

switch position 

d

>

RE

) is periodically checked, the 

replacement can take place before the fault is triggered.

For an activated filter replacement the ASD is set to the 

isolate

” state. This insures that during the replacement 

work falling dust particles from the filter element do not 

cause a false alarm.

When the ASD 533 housing is closed, the “Start filter replacement” 

function can be activated by means of the 

“Reset” key

(provided 

the filter monitoring is activated). To do so, press the key 

longer

than 15 s

(attention: lamp test after 10 s). After 15 s the filter re-

placement is started and indicated by switching to the “Isolate” 

state (Fault and LED “Fault”). When the “Reset” key is deactivated 

(via ASD Config), the “Start filter replacement” function is not ac-

cessible.
After the filter has been replaced, the “Filter replacement” proce-

dure is completed by pressing the 

“Reset” key

on the ASD. This 

cancels the “Isolate” state and resets the fault on the ASD. “Filter 

service life” monitoring is restarted at 0.
The filter replacement can also be started via 

EasyConfig

switch 

position 

d

>

SE

. For information please refer to Technical Descrip-

tion T 140 287, Section 7.8.

Measurements / commissioning protocol

Carry out the following measurements:

Measure voltage at terminals 1 (+), 2 (-) (also terminals 3 and 4

in the case of a redundant voltage supply) 

target value =

12.3 to 13.8 (in 12 VDC operation) and 21.6 to 27.6 VDC (in

24 VDC operation)

Airflow value in switch positions 

V

(see also Technical descrip-

tion, T 140 287, Sec. 7.6.1).

The commissioning protocol is like a personal history of the 

ASD 533 and should therefore be filled out conscientiously and 

completely and stored in the ASD 533. If required, a copy can be 

made and stored in the installation dossier.

Содержание ASD 533

Страница 1: ... 35 Memory Card Module The ASD 533 can be connected to a higher level FACP via poten tial free change over contacts Fitting an XLM 35 or SLM 35 means that the ASD 533 can be ide ally connected to the SecuriFire and Integral fire alarm systems via the addressable loop with SLM also to the SecuriPro The RIM 35 is available as a further installation option This mod ule enables the availability of all...

Страница 2: ...allation of the ASD release the two lock clamps however it should be left inside its protective packaging until the definitive commissioning The definitive installation is carried out as de scribed below see Fig 3 Always leave the smoke sensor inside its protective packaging until it is ready to be installed definitively in the detector housing Depending on the circumstances e g long period of tim...

Страница 3: ...manently assigned parameters Normative system limits according to EN 54 20 Class A to C positions A11 to C31 Non normative system limits positions W01 to W44 Configurable positions for settings after using ASD PipeFlow and or ASD Config or SecuriPro SecuriFire or Integral FACP SLM 35 XLM 35 X01 to X03 The parameters are saved at the factory with values for compliance with EN 54 20 Changing the par...

Страница 4: ...ior consultation with the manufacturer The airflow monitoring values stored under those switch positions are not tested in accordance with EN For more information on using the table of system limits please refer to the Technical description T 140 287 Sec 4 4 4 3 and 4 4 4 4 Table of system limits for planning without ASD PipeFlow calculation Compliant with EN 54 20 Class A highly sensitive Shape S...

Страница 5: ... 5 3 0 7 0 11 2 0 2 0 2 0 2 0 2 5 2 5 2 5 2 5 2 5 4 0 7 0 12 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 2 5 2 5 4 0 7 0 U T shaped sampling pipes Number of sam pling holes per sampling branch Hole diameter in mm for the sampling hole number as of ASD 1 2 3 4 5 6 7 8 1 5 0 2 4 0 5 0 3 4 0 4 0 5 0 4 4 0 4 0 4 0 5 0 5 4 0 4 0 4 5 5 0 6 5 6 3 0 3 0 3 5 3 5 4 0 6 5 7 2 5 3 0 3 0 3 5 3 5 4 0 6 5 8 2 5 2 5 3 0 3 0 ...

Страница 6: ... 5 60 5 X01 X03 Soiling threshold of Al 75 65 100 5 X01 X03 Dust latching On On Off X01 X03 Soiling latching On On Off X01 X03 Smoke sensor fault delay 30 s 0 s 60 s 1 s X01 X03 Airflow monitoring LS Ü pipe blockage On Off On On Off X01 X03 LS Ü pipe breakage On Off On On Off X01 X03 LS Ü sensitivity applies to A01 to C31 20 1 70 1 X01 X03 LS Ü value averaging number 20 1 30 1 X01 X03 LS Ü delay a...

Страница 7: ...al 1 s 1 120 s MCM smoke peak value memory Off Off On Carry out new initial reset On Off Smoke sensor mode of operation smoke sensor I SSD DMB SSD DMB or OEM inputs individual or in combination Switched off Isolate smoke sensor smoke sensor I Normal operation Isolate normal operation Filter monitoring smoke sensor I Off Off On Filter service life 6 months 1 24 months Read out operation time months...

Страница 8: ... b21 Displays the new set ting Initial reset Measure Display Procedure remarks Before carrying out an initial reset i e after switching on the ASD 533 make sure you observe a waiting time of at least 5 min 1 Press the UP key flashing C31 or others Displays the default setting or the installa tion specific switch position 2 Press the UP key several times until dis play shows U in succession A to U ...

Страница 9: ...200006 01 XX SecuriLine eXtended line module XLM 35 11 2200003 01 XX SecuriLine module SLM 35 4000286 0101 Relay interface module RIM 35 4000287 0101 Memory card module MCM 35 4000285 0101 SD memory card industrial version 11 4000007 01 XX USB cable 4 5 m 4301248 Main board AMB 33 1 11 2200004 01 XX BCB 35 without smoke level indicator 4301220 0101 Aspirating fan unit AFU 35 complete 4000299 Airfl...

Страница 10: ... C Sampling pipe temperature range 20 60 C Max permissible temperature fluctuation in detector housing and sampling pipe operation 20 C Max permissible storage temperature for detector housing without condensation 20 70 C Ambient pressure difference between detector housing and sampling pipe sampling holes must be identical Humidity ambient condition for detector housing transient without condensa...