![IMO VXSM150-1 Скачать руководство пользователя страница 67](http://html.mh-extra.com/html/imo/vxsm150-1/vxsm150-1_instruction-manual_2048149067.webp)
5-38
Selecting Functions
5
A: Alternative motor parameters
Maximum frequency 2
The maximum frequency output by the inverter
for motor 2. This parameter functions in the
same way as F03 "Maximum output frequency
1". For the description, refer to F03 "Maximum
output frequency 1".
Base frequency 2
The maximum output frequency in the constant
torque zone of motor 2, that is, the output
frequency at the rated output voltage. This
parameter functions in the same way as F04
"Base frequency 1". For the description, refer to
F04 "Base frequency 1".
Rated voltage 2 (at base
frequency 2)
The rated output voltage supplied to motor 2.
This parameter functions in the same way as
F04 "Rated voltage 1". For the description, refer
to F05 "Rated voltage 1".
Maximum voltage 2 (at maximum
frequency 2)
The maximum output voltage of the inverter for
motor 2. This parameter functions in the same
way as F06 "Maximum voltage 1". For the
description, refer to F06 "Maximum voltage 1".
Torque boost 2
The torque boost function of motor 2. This
parameter functions in the same way as F09
"Torque boost 1". For the description, refer to
F09 "Torque boost 1".
Electronic thermal overload relay for
motor 2 (Select)
Electronic thermal overload relay for
motor 2 (Level)
Electronic thermal overload relay for
motor 2 (Thermal time constant)
The electronic thermal overload relay functions
of motor 2. These parameters function in the
same way as F10 through F12 Electronic
thermal overload relay for motor 1. For the
description, refer to F10 through F12.
Torque vector control 2
The torque vector function of motor 2. This
parameter functions in the same way as F42
"Torque vector control 1". For the description,
refer to F42 "Torque vector control 1".
A09
A08
A07
A06
A05
A04
A03
A02
A01
Maximum temperature of heat sink
•
The maximum value in each hour is displayed
in degree C.
Maximum effective current
•
The maximum value in each hour is displayed
in A.
Main circuit capacitor life
•
The capacity of the capacitor in the main
circuit is displayed in %. For the measuring
conditions, refer to section 8-2 (1)
"Measurement of capacitance of capacitor in
main circuit".
Cooling fan operation time
•
Integral hours is displayed. The displayed
time is 0 to 6500, indicating 0 to 65000 hours.
(Though the displayed value is in ten hours,
the inverter adds each hour. Operation
shorter than one hour is not counted.)
Inverter ROM version
•
The version of the software of the inverter is
displayed.
Keypad panel ROM version
•
The version of the software of the keypad
panel is displayed.
Option ROM version
•
For inverters with optional equipment, the
version of the optional software is displayed.
H46
H45
H44
H43
H42
H41
H40
Содержание VXSM150-1
Страница 3: ......
Страница 41: ...5 12 Selecting Functions 5 Frequency setting block diagram ...
Страница 45: ...5 16 Selecting Functions 5 Note The chain line indicates the motor speed ...
Страница 71: ...7 1 Troubleshooting 7 7 Troubleshooting 7 1 When Protective Function Activates 1 Overcurrent ...
Страница 72: ...Troubleshooting 7 2 7 2 Overvoltage 3 Undervoltage ...
Страница 77: ...7 7 Troubleshooting 7 3 The motor loses speed during acceleration 4 Excessive heat generation from motor ...