2-7
Installation and Connection
2
Classifi-
Terminal
cation
symbol
Terminal name
Description of function
FM
Analog monitor
The monitor signal for analog DC voltage (0 to +10
Vdc) is output. The signal description can be
selected from the following.
• Output frequency1 (before slip compensation)
• Output frequency2 (after slip compensation)
• Output current
• Output voltage
• Output torque
• Load factor
Analog
• Input power
• PID feedback value
output/
• DC link circuit voltage
pulse
* Allowable connection impedance: min. 5 k ohm
output
Pulse rate monitor
The monitor signal is output according to the pulse
voltage. The signal description is the same as the
FMA signal.
* Allowable connection impedance: min. 5 k ohm
Use SW1 on the control board and function code
F29 to change between the analog monitor and
Pulse rate monitor.
(FMA: analog monitor, FMP: Pulse rate monitor)
Y1E
Transistor output 1
The RUN signal, frequency equivalence signal,
Y2E
Transistor output 2
overload early warning signal and other signals are
output to arbitrary ports at a transistor output.
Refer to terminal function E20 to 21 setting
methods in section 5-2 Detail Description of Each
Function.
<Transistor output circuit specification>
Transistor
output
CMC
Common
Common for transistor output signal. Isolated from
(Transistor output)
terminals CM and 11.
P24
DC voltage supply
Power supply for transistor output load. (24 Vdc 50
mAdc Max.) (When using P24, short the CMC and
P24 terminals) (If the P24 terminal is overloaded or
connected with the CM terminal, the inverter trips
with Er3 indication. To reset, remove external
causes and, after several minutes, turn the inverter
on again.)
30A,30B,
Alarm relay output
When the inverter is stopped with an alarm, a relay
30C
contact output (1C) is issued.
Relay
Contact capacity: 48 Vdc 0.5 A
output
(When complying with UL/cUL:42Vdc 0.5A)
Selection between excitation upon an alarm or
excitation during normal operation is possible.
Item
min.
typ.
Max
Operation
Level OFF
-
-1V
-2V
voltage *1
Level ON
-
-24V
-27V
Max. load current at ON
-
-
-50mA
Leakage current at OFF
-
-
-0.1mA
Operation Voltage
Current
Содержание VXSM150-1
Страница 3: ......
Страница 41: ...5 12 Selecting Functions 5 Frequency setting block diagram ...
Страница 45: ...5 16 Selecting Functions 5 Note The chain line indicates the motor speed ...
Страница 71: ...7 1 Troubleshooting 7 7 Troubleshooting 7 1 When Protective Function Activates 1 Overcurrent ...
Страница 72: ...Troubleshooting 7 2 7 2 Overvoltage 3 Undervoltage ...
Страница 77: ...7 7 Troubleshooting 7 3 The motor loses speed during acceleration 4 Excessive heat generation from motor ...