- The power data provided in the table is ob-
tained with 0.5 m long intake/exhaust pipe.
- Gas flow rates refer to heating output below a
temperature of 15°C and pressure of 1013 mbar.
- Burner pressure values refer to use of gas at
15°C.
- The number of revs for the fan on the display
is expressed in revs / 50 (Ex.: 1000 revs = 20).
Victrix Pro 100 2ErP.
METHANE (G20)
PROPANE (G31)
HEAT OUTPUT
HEAT OUTPUT
BURNER GAS FLOW
RATE
REVS
FAN
BURNER GAS FLOW
RATE
REVS
FAN
(kW)
(kcal/h)
(m
3
/h)
(n°)
(kg/h)
(n°)
90.0
77400
9.77
6700
7.17
6350
87.0
74820
9.44
6470
6.93
6140
84.0
72240
9.11
6230
6.68
5930
81.0
69660
8.78
6000
6.44
5730
78.0
67080
8.45
5780
6.20
5530
75.0
64500
8.12
5560
5.96
5320
72.0
61920
7.79
5340
5.72
5130
69.0
59340
7.47
5120
5.48
4930
66.0
56760
7.14
4910
5.24
4730
63.0
54180
6.82
4700
5.00
4540
60.0
51600
6.49
4490
4.77
4340
57.0
49020
6.17
4280
4.53
4150
54.0
46440
5.85
4080
4.29
3960
51.0
43860
5.52
3880
4.05
3770
48.0
41280
5.20
3680
3.82
3580
45.0
38700
4.88
3480
3.58
3400
42.0
36120
4.56
3290
3.34
3210
39.0
33540
4.23
3090
3.11
3030
36.0
30960
3.91
2900
2.87
2840
33.0
28380
3.59
2710
2.63
2660
30.0
25800
3.27
2530
2.40
2480
27.0
23220
2.94
2340
2.16
2300
24.0
20640
2.62
2160
1.92
2120
21.0
18060
2.30
1980
1.68
1940
18.0
15480
1.97
1800
1.45
1760
15.0
12900
1.64
1630
1.21
1580
12.0
10320
1.32
1450
0.97
1400
9.4
8084
1.03
1300
0.76
1250