background image

35

3-11

+

+

3

12

1

P1

2

P3

3

12

P1

1

2 P3

INS

TALLER

US

ER

MAINTEN

AN

CE TECHNI

CI

AN

3.10 CONVERTING THE BOILER TO 

OTHER TYPES OF GAS.

If the boiler has to be converted to a different gas 

type to that specified on the data plate, request 

the relative conversion kit for quick and easy 

conversion.

The gas conversion operation must be carried 

out by an authorised company (e.g. Immergas 

After-Sales Technical Assistance Service).

To convert to another type of gas the following 

operations are required:

- disconnect the appliance;
- Change the sleeve with Venturi (det. 21 fig. 

1-25);

- change the gas nozzle (det. 4 fig. 1-25);
- re-power the appliance;
-  regulate the maximum heat output by varying 

the number of fan revs. (parameter P25 “Max 

number of fan revs in CH mode”) according to 

par. 3.24;

- regulate the minimum heat output by varying 

the number of fan revs. (parameter P26 “Min 

number of fan revs in CH mode”) according to 

par. 3.24;

- activate the chimney sweep function;
- check the CO

2

 value on the table in par. 3.25, 

especially:

  -  check the CO

2

 value in the flue with chimney 

sweep at 0%;

  -  check the CO

2

 value in the flue with chimney 

sweep at 100%;

- exit the chimney sweep function;
- seal the gas flow rate regulation devices (if 

settings are modified);

- after completing the conversion, apply the 

sticker, contained in the conversion kit, near 

the data-plate. Using an indelible marker pen, 

cancel the data relative to the old type of gas.

These adjustments must be made with reference 

to the type of gas used.

3.11 CHECKS FOLLOWING 

CONVERSION TO ANOTHER TYPE 

OF GAS.

After making sure that transformation was 

carried out with the Venturi and a nozzle of 

suitable diameter for the type of gas used and 

the calibration has been performed at the correct 

num. of revs, check that:

-  the burner flame is not too high and that it is 

stable (does not detach from burner)

- there are no leaks from the gas circuit.

N.B.:

 all boiler adjustment operations must 

be carried out by a qualified technician (e.g. 

Immergas After-Sales Assistance).

3.12 ADJUSTMENT OF THE AIR-GAS 

RATIO.

Calibration of minimum CO

2

Turn the boiler on and start the chimney sweep 

functions at minimum output (0%). To have an 

exact value of CO

2

 the technician must insert 

the sampling probe to the bottom of the sample 

point, then check that the CO

2

 value is that 

specified in the table in par. 3.25, on the con-

trary, regulate the screws (3 fig. 3-11) (Off-Set 

regulator). To increase the CO

2

 value, turn the 

adjustment screw (3) in a clockwise direction and 

vice versa to decrease it.
Calibration of maximum CO

2

.

When you finish the minimum CO

2

 adjustment, 

turn the boiler on and start the chimney sweep 

function at the maximum output (100%). To have 

an exact value of CO

2

 the technician must insert 

the sampling probe to the bottom of the sample 

point, then check that the CO

2

 value is that spec-

ified in the table in par. 3.25, otherwise, adjust 

the screw (12 fig. 3-11) (gas flow rate regulator).

To increase the CO

2

 value, turn the adjustment 

screw (12) in an anti-clockwise direction and vice 

versa to decrease it.

At every adjustment variation on the screw (12) 

it is necessary to wait for the boiler to stabilise 

itself at the value set (about 30 sec.).

3.13 CH OUTPUT ADJUSTMENT.

If it is necessary to change the CH output, you 

will need to adjust the “P08” maximum CH out-

put and “P09” minimum CH output parameters.

To check the regulated heat output value, com-

pare the no. of fan revs with that in the table 

(par. 3.24).

3.14 OUTPUT ADJUSTMENT DURING 

DHW (ONLY IN COMBINATION 

WITH AN OPTIONAL EXTERNAL 

STORAGE TANK).

If it is necessary to change the DHW output, 

you will need to adjust the “P20” maximum 

DHW output and “P21” minimum DHW output 

parameters.

To check the regulated heat output value, com-

pare the no. of fan revs with that in the table 

(par. 3.24).

Key:

  1  -  Gas valve inlet pressure point

  2  -  Gas valve outlet pressure point

  3  -  Off/Set adjustment screw

  12  -  Outlet gas flow rate regulator

8222 Gas Valve (Victrix Pro 100 - 120 2ErP)

848 Gas Valve (Victrix Pro 80 2ErP)

Содержание Victrix Pro 100 2ErP

Страница 1: ...VICTRIX PRO 80 100 120 2 ErP IE Instruction and warning book 1 041665ENG...

Страница 2: ......

Страница 3: ...in the regulations in force and principles of good practice In compliance with legislation in force the systems must be designed by qualified professionals within the dimensional limits established b...

Страница 4: ...panel 23 2 5 Using the boiler 23 2 6 Troubleshooting 25 2 7 Info menu 27 2 8 Boiler shutdown 27 2 9 Restoring central heating system pressure 27 2 10 System drainage 27 2 11Anti freeze protection 27...

Страница 5: ...dequate support if inserted correctly according to technical standards in walls made of solid or semi hollow brick or block In the case of walls made from hollow brick or block partitions with limited...

Страница 6: ...l kits that can be potentially connected to the boiler must be protected on the basis of their electrical protection rating 1 5 ANTI FREEZE PROTECTION Minimum temperature 5 C The boiler comes standard...

Страница 7: ...tanks in case of supply from LPG depot New LPG storage tanks may contain residual inert gases nitrogen that degrade the mixture delivered to the appliance causing problems with boiler operation Due t...

Страница 8: ...tem as specified by current safety standards Attention Immergas S p A declines any respon sibility for damage or physical injury caused by failure to connect the boiler to an efficient earth system or...

Страница 9: ...at the On Off thermostat contact is of the clean type i e independent of the mains voltage otherwise the P C B would be damaged Cascade and zone regulator must be connected through clamps 37 and 38 to...

Страница 10: ...chamber and fan assisted The boiler leaves the factory with B23 configuration to change the configuration of the boiler to type C sealed chamber and fan assisted disassemble the 80 adapter the bracke...

Страница 11: ...1 3 m Terminal complete with vertical ex haust 80 Exhaust m 3 DUCT TYPE Equivalent length in m of concentric pipe 80 125 Concentric pipe 80 125 m 1 1 0 m Concentric bend 90 80 125 1 9 m Concentric ben...

Страница 12: ...er to ensure sufficient space to carry out the tests required by law upon commissioning External grid The intake exhaust terminal if properly installed is pleasant to look at on the outside of the bui...

Страница 13: ...he lid using the previously disassembled sheet steel plate 3 Installation of the fake aluminium tile replace the tiles with the aluminium sheet 5 shaping it to ensure that rainwater runs off Position...

Страница 14: ...ith this configuration can be extended up to a max measurement of 28 0 m with Victrix Pro 80 2ErP 14 0 m with Victrix Pro 100 2ErP and 8 5 m with Victrix Pro 120 2ErP including the terminal Using the...

Страница 15: ...late has been fitted This will ensure sealing and joining of the elements making up the kit Horizontal kit 80 with exhaust in flue Kit assembly Fig 1 21 install the 80 bend 1 with the male side smooth...

Страница 16: ...rent technical regulations in particular the declaration of conformity must be compiled at the end of work and on commissioning of the ducted system The instructions in the project or technical report...

Страница 17: ...In domestic hot water mode the circulator pump always runs at maximum speed Pump release If after a prolonged period of inactivity the circulation pump is blocked unscrew the front cap and turn the mo...

Страница 18: ...A B INSTALLER USER MAINTENANCE TECHNICIAN Head available to the system Head kPa Head kPa Flow rate l h Flow rate l h Key A Available head B Power absorbed by the circulator pump dotted area Circulato...

Страница 19: ...e 10 Flue probe 11 Condensation module 12 Air pressure switch 13 Fumes hood 14 Air intake pipe 15 Igniter 16 Heat exchanger safety thermostat manual reset 17 Heat exchanger safety thermal fuse 18 Igni...

Страница 20: ...d block circuit breaker switches andofthethermometer notsuppliedasstandard with the boiler must be set up as described in the installation instructions in compliance with theprovisionsofthe R collecti...

Страница 21: ...tral heating circuit pump CMI 1 13 Zone 2 central heating circuit pump CMI 2 14 Zone 3 direct circuit pump CD 15 Storage tank unit feeding pump 16 Zone 1 safety thermostat CMI 1 17 Zone 2 safety therm...

Страница 22: ...orary shutdown of the boiler is required proceed as follows a drain the heating system if anti freeze is not used b shut off all electrical water and gas supplies N B in the case of maintenance interv...

Страница 23: ...indicates a base value at which the system has been designed and calculated and however not less than 0 5 bar Open the gas cock upstream from the boiler Turn the main switch and the boiler runs a self...

Страница 24: ...5 2 6 DHW exclusion with the boiler set up for DHW heating press C momentarily to exclude DHW heating mode operation To restore DHW heating press C again Anomaly records press and hold C down to acce...

Страница 25: ...t During boiler operation the board does not detect a change in the flow NTC probe temperature The error may be caused by a poor thermal probe contact or a system with excessive thermal inertia Press...

Страница 26: ...rn temperatures The error may be caused by a failure in one of the two probes 2 1 0E98 Simple cascade com munication anomaly Occurs if the communication between the display boards breaks down Check th...

Страница 27: ...drained completely or antifreeze substances must be added to the heating system water In systems that are drained frequently filling must be carried out with suitably treated water to eliminate hardn...

Страница 28: ...ction ing of fans check that the intake and or exhaust terminals are not blocked ensure activation of all adjustment devices seal the gas flow rate regulation devices if settings are modified check se...

Страница 29: ...Main switch X90 Boiler configuration jumper Y1 Gas valve Configure the corresponding parameters when connecting in simple cascade or when con necting in system side flow probe or D H W pump 1 Externa...

Страница 30: ...DIAGRAM Key A2 Electronic board A4 Display board B1 Flow probe B1 2 System side flow probe optional B2 Domestic hot water probe optional B4 External temperature probe optional B5 Return probe B10 Flue...

Страница 31: ...probe NTC B2 Domestic hot water probe NTC B4 External probe M2 Plant CH pump M30 3 way valve Note probe B1 2 B2 B4 Connection cable diameter 3 7 mm Cable section 0 5 1 5 mm2 1 External relay optional...

Страница 32: ...tage of CO2 in flue gases The over temperature safety thermostat the flow probe or the return probe are triggered frequently It can depend on the lack of water in the boiler little water circulation i...

Страница 33: ...ower in the event of simple cascade 0 255 kW 80 kW 75 100 kW 90 120 kW 115 P14 External probe curve This is used to select the external probe operating curve optional 0 disabled probe 0 10 0 P15 Exter...

Страница 34: ...31 Unit of measurement This defines the unit of measure on the display whether metric or Imperial 0 127 C kW 128 256 F kBTu h 0 P32 Set Resc Min Limits the minimum value of the heating set The paramet...

Страница 35: ...ler adjustment operations must be carried out by a qualified technician e g Immergas After Sales Assistance 3 12 ADJUSTMENT OF THE AIR GAS RATIO Calibration of minimum CO2 Turn the boiler on and start...

Страница 36: ...e request is deactivated below 1 V Notes If P37 is set at 0 it is not active when the boiler is in stand by or summer mode The calculated set is limited by the P02 20 C range Themaximumandminimumtempe...

Страница 37: ...replaced at least every two years regardless of their state of wear Check that the burner is intact that it has no deformations or cuts and that it is properly fixed to the combustion chamber lid oth...

Страница 38: ...to de tach it from the central hooks and then slide it downwards take the two clamping screws out 4 from the control panel with their rings 5 press the two side hooks 7 and tilt the control panel 6 re...

Страница 39: ...39 3 15 1 6 8 9 9 12 12 10 11 13 13 13 13 A A Rif A 7 7 INSTALLER USER MAINTENANCE TECHNICIAN Ref A...

Страница 40: ...03 5620 61 0 52460 6 63 5550 4 87 5440 59 0 50740 6 42 5380 4 71 5270 57 0 49020 6 20 5210 4 55 5090 55 0 47300 5 98 5040 4 39 4920 53 0 45580 5 76 4880 4 23 4750 51 0 43860 5 55 4710 4 07 4580 49 0 4...

Страница 41: ...230 6 68 5930 81 0 69660 8 78 6000 6 44 5730 78 0 67080 8 45 5780 6 20 5530 75 0 64500 8 12 5560 5 96 5320 72 0 61920 7 79 5340 5 72 5130 69 0 59340 7 47 5120 5 48 4930 66 0 56760 7 14 4910 5 24 4730...

Страница 42: ...63 0 54180 6 83 4100 5 01 4000 60 0 51600 6 51 3930 4 78 3830 57 0 49020 6 18 3760 4 54 3660 54 0 46440 5 86 3590 4 30 3490 51 0 43860 5 54 3430 4 06 3330 48 0 41280 5 21 3260 3 83 3160 45 0 38700 4 8...

Страница 43: ...mbar mm H2 O 20 204 37 377 Flue flow rate at nominal heat output kg h 146 148 Flue flow rate at min heat output kg h 16 16 CO2 at Q Nom Min 9 40 9 00 10 60 10 10 CO with 0 O2 at Nom Min Q Nom Min ppm...

Страница 44: ...07 6 107 2 107 5 Heat loss at casing with burner On Off 80 60 C 0 34 0 80 0 41 0 60 0 28 0 70 Heat loss at flue with burner On Off 80 60 C 0 01 2 2 0 01 1 9 0 01 2 0 Central heating circuit max operat...

Страница 45: ...Md Model code Sr N Serial Number CHK Check Cod PIN PIN code Type appliance configuration ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn...

Страница 46: ...60 C on return and 80 C on flow Low temperature mode for condensation Boilers means 30 C for low temperature boilers 37 C and for other appliances 50 C of return temper ature Model s Victrix Pro 100...

Страница 47: ...a low temperature mode P1 33 3 kW At 30 of nominal heat output in a low temperature mode 1 96 5 Auxiliary electricity consumption Other items At full load elmax 0 190 kW Heat loss in standby Pstby 0 1...

Страница 48: ...mmergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 041665ENG rev ST 003520 000 08 18 Inglese p...

Отзывы: