The kit includes:
1 - 90° 80 Ø bend (1)
1 - 80 Ø exhaust terminal (2)
1 - Internal ring (3)
1 - External ring (4)
1.17 INSTALLATION OF 80 Ø
HORIZONTAL TERMINALS.
Configuration type B, open chamber and
forced draught.
80 Ø horizontal kit with wall flue exhaust.
Kit assembly (Fig. 1-19): install the 80 Ø bend (1)
with the male side (smooth) fully home on the
central hole of the boiler. Fit the exhaust terminal
(2) with the male end (smooth) to the female
end of the bend (1) up to the stop; making sure
that the internal (3) and external (4) wall sealing
plate has been fitted. This will ensure sealing and
joining of the elements making up the kit.
Horizontal kit 80 Ø with exhaust in flue.
Kit
assembly (Fig. 1-21): install the 80 Ø bend (1)
with the male side (smooth) fully home on the
central hole of the boiler. Fit the exhaust pipe (2)
with the male end (smooth) to the female end of
the bend (1) up to the stop; making sure that the
internal wall sealing plate (3) has been fitted. This
will ensure sealing and joining of the elements
making up the kit.
• Maximum length (MAX L) (Fig. 1-20 and 22).
The kit with this configuration can be extended
up to a
max. measurement of 28.0 m with Victrix
Pro 80
2ErP
, 14.0 m with Victrix Pro 100
2ErP
and 8.5 m with Victrix Pro 120
2ErP, including
the terminal.
The kit includes:
1 - 90° 80 Ø bend (1)
1 - 80 Ø drain pipe (2)
1 - Internal ring (3)
Minimum slope 1.5 %