The kit includes:
1 - Adaptor 80/125 Ø (1)
1 - Gasket (2)
1 - Concentric bend 80/125 Ø at 87° (4)
1 - Int./exhaust concentric terminal
80/125 Ø (5)
1 - Internal ring (6)
1 - External ring (7)
1.14 CONCENTRIC HORIZONTAL KIT
INSTALLATION.
Type C configuration, sealed chamber and
fan assisted.
Installation of this terminal must comply with
the provisions set forth by all of the legislation
and regulations in force that may allow, in certain
cases, wall flue exhaust for low-NOx condensing
boilers.
The position of the terminal (in terms of dis-
tances from openings, overlooking buildings,
decking, etc.) must be set up in compliance with
regulations in force as well as the references of
good technique.
This terminal is connected directly to the outside
of the building for air intake and flue exhaust. The
horizontal kit can be installed with the rear, right
side, left side or front outlet. For installation with
frontal outlet, one must use the fixing plate and
a concentric bend coupling in order to ensure
sufficient space to carry out the tests required
by law upon commissioning.
• External grid. The intake/exhaust terminal,
if properly installed, is pleasant to look at on
the outside of the building. Make sure that
the external silicone sealing plate is properly
inserted in the wall.
Horizontal intake-exhaust kit Ø 80/125
Kit
assembly (Fig. 1-10): install the 80/125 Ø adapter
(1) on the central hole of the boiler fully home.
Slide the gasket (2) along the adapter (1) up to
the relevant groove, fix it to the lid using the pre-
viously disassembled sheet steel plate (3) Engage
the bend (4) with the male side (smooth) until it
is fully home on the adapter (1). Fit the 80/125
Ø (5) concentric terminal pipe with the male
end (smooth) to the female end of the bend (4)
(with lip seals) up to the stop; making sure that
the internal (6) and external wall sealing plates
(7) have been fitted, this will ensure sealing and
joining of the elements making up the kit.
• Maximum length (MAX L) (Fig. 1-11). The kit
with this configuration can be extended up to
a
max. measurement of 11.0 m with Victrix Pro
80
2ErP
, 8.0 m with Victrix Pro 100
2ErP
and
5.0 m with Victrix Pro 120
2ErP, including the
grid-covered terminal and the concentric bend
on the boiler outlet.