background image

29

3-3

3-4

1

4

3

2

INS

TALLER

US

ER

MAINTEN

AN

CE TECHNI

CI

AN

Key:

  1  -  Fuse 3.15 AF

  2  -  Removable memory 

(A1

9

)

P.C.B.

GAS valve SGV 100 B

&

P

Key:

  1  -  Gas valve outlet pressure point

  2 -  Coil

  3  -  Wiring connector

  4  -  Gas valve inlet pressure point

Comando Amico Remoto

V2

: the boiler is 

prepared for the application of the Comando 

Amico Remoto remote control 

V2

 (CAR

V2

), which 

must be connected to clamps 41 and 44 of the 

terminal board (located in the boiler control 

panel) respecting the polarity and eliminating 

jumper X40.
Room thermostat: the boiler is prepared for the 

application of the room thermostat (S20), which 

must be connected to clamps 40 and 41 of the 

terminal board (located in the boiler control 

panel) eliminating jumper X40.
The connector X5 is used for the connection to 

the relay board.
The connector X6 is for connection to a personal 

computer.
The connector X8 is used for software updating 

operations.

3.3  REMOVABLE MEMORY

The P.C.B. is equipped with a removable memory 

(2 Fig. 3-4), which records all operation param-

eters and system customisations.

Should the P.C.B. be replaced, you can use the 

memory of the replaced board again, so it is not 

necessary to reconfigure the appliance.

Attention:

 replacing the memory must be carried 

out after disconnecting all electrical connection 

of the P.C.B.

3.4 TROUBLESHOOTING.

N.B.:

 maintenance operations must be carried 

out by an authorised company (e.g. Authorised 

After-Sales Technical Assistance Service).
-  Smell of gas. Caused by leakage from gas circuit 

pipelines. Check sealing efficiency of gas intake 

circuit.

- Repeated ignition blocks. No gas, check the 

presence of pressure in the network and that 

the gas adduction cock is open. 

- Irregular combustion or noisiness. It may be 

caused by: a dirty burner, incorrect combustion 

parameters, intake-exhaust terminal not cor-

rectly installed. Check the above components.

- Non-optimal ignition of first ignition of the 

burner: even if the burner is perfectly calibrat-

ed, first ignition of the burner (after calibration) 

can be sub-optimal; the system automatically 

regulates ignition until it finds optimal ignition 

of the said burner.

- Frequent interventions of the overheating 

safety thermostat. It can depend on the lack 

of water in the boiler, little water circulation 

in the system or blocked pump. Check on the 

manometer that the system pressure is within 

established limits. Check that the radiator 

valves are not closed and also the functionality 

of the pump.

- Drain trap clogged. This may be caused by 

dirt or combustion products deposited inside. 

Check that there are no residues of material 

blocking the flow of condensate.

-  Heat exchanger clogged. This may be caused by 

the drain trap being blocked. Check that there 

are no residues of material blocking the flow of 

condensate.

- Noise due to air in the system. Check open-

ing of the special air vent valve cap (Part. 24 

Fig. 1-29). Make sure the system pressure and 

expansion vessel pre-charge values are within 

the set limits; The factory-set pressure values of 

the expansion vessel must be 1.0 bar, the value 

of system pressure must be between 1 and 1.2 

bar.

- Noise due to air inside the condensation 

module. Use the manual air vent valve (Part. 

13 Fig. 1-29) to eliminate any air present in the 

condensation module. When the operation has 

been performed, close the manual vent valve.

- Poor production of D.H.W. If a drop in per-

formance is detected during supply of D.H.W., 

it is possible that the condensation module 

or D.H.W. heat exchanger is clogged. In this 

case, contact Immergas After-Sales Assistance 

Service that has procedures to clean the module 

or D.H.W. heat exchanger.

3.5  CONVERTING THE BOILER TO 

OTHER TYPES OF GAS.

If the boiler has to be converted to a different type 

of gas to that specified on the data nameplate, 

proceed as follows:

The gas conversion operation must be carried 

out by an authorised company (e.g. Authorised 

Technical After-Sales Service).

To convert to another type of gas the following 

operations are required:

-  Select, via programming menu “G”, the type of 

gas by selecting “nG” for methane gas and “LG” 

for LPG gas. (See par. 3.12).

- Carry out complete calibration (see par. 3.8); 

during the procedure check and, if necessary, 

correct the air - gas ratio.

- Upon completing the conversion, apply the 

sticker regarding the modified gas content onto 

the data nameplate in the connection box.

These adjustments must be made with reference 

to the type of gas used, following that given in 

the table (Par. 3.22).

3.6  CHECKS FOLLOWING 

CONVERSION TO ANOTHER TYPE 

OF GAS.

After having made sure that the conversion is 

complete and that the calibration has been suc-

cessful, you must make sure that:

- there is no flame in the combustion chamber
-  the burner flame is not too high or low and that 

it is stable (does not detach from burner)

- the pressure testers used for calibration are 

perfectly closed and there are no leaks from 

the gas circuit.

N.B.:

 all boiler adjustment operations must be 

carried out by a qualified company (e.g. Author-

ised After-Sales Assistance).

Содержание Victrix Maior 28 TT 1 ErP

Страница 1: ...VICTRIX MAIOR 28 35 TT 1 ERP IE Instruction and recommendation booklet 1 038659ENG...

Страница 2: ......

Страница 3: ...onal limits established by the Law Installation and maintenance must be performed in compliance with the regulations in force according to the manufacturer s instructions and by an authorised company...

Страница 4: ...on recommendations 5 1 2 Main dimensions 6 1 3 Antifreeze protection 6 1 4 Boiler connection unit 7 1 5 Gas connection 7 1 6 Hydraulic connection 7 1 7 Electric connection 8 1 8 Remote controls and ro...

Страница 5: ...boilerforpossiblewater and flue removal connections Keep all flamma ble objects away from the appliance paper rags plastic polystyrene etc Do not place household appliances underneath the boiler as th...

Страница 6: ...ary with respect to the minimum temperature at which the system must be kept An aqueous solution must be made with potential pollution class of water 2 EN 1717 2002 or local regula tions in force Atte...

Страница 7: ...n compliance with the tech nical standards in force in order to protect the system and the appliance from deposits e g scale slurry or other hazardous deposits In order not to void the heat exchanger...

Страница 8: ...d assembly instructions contained in the acces sory kit On Off Immergas digital chrono thermostat The chrono thermostat allows set two room temperature value one for daytime comfort temperature and on...

Страница 9: ...e always operates when con nected regardless of the presence or type of room chrono thermostat used and can work in combi nation with Immergas chrono thermostats The correlation between system flow te...

Страница 10: ...ctor allowed corresponds to the resistance encountered with the maximum allowed pipe length for each type of Terminal Kit This information allows calculations to be made to verify the possibility of s...

Страница 11: ...Intake and Exhaust 16 3 m 2 5 Intake m 18 7 Exhaust m 4 9 m 7 7 Exhaust m 13 6 Concentric vertical intake exhaust terminal 60 100 Intake and Exhaust 9 m 1 4 Intake m 10 3 Exhaust m 2 7 m 4 3 Exhaust m...

Страница 12: ...s present in the kit positioning the relevant gaskets Engage the 90 80 bend with the male end smooth in the female end with lip seal of the 80 flange unit until it stops Introduce the gasket making it...

Страница 13: ...the circular projections down wards in contact with the boiler flange and tighten using the screws present in the kit Fit the 60 100 3 concentric terminal pipe with the male side smooth to the female...

Страница 14: ...cal length of 14 4 m including the terminal This configuration corresponds to a resistance factor of 100 In this case specific extensions must be requested Vertical kit with aluminium tile 80 125 Kit...

Страница 15: ...t Remove the flat flange present in the lateral hole with respect to the central one ac cording to needs and replace it with the flange 3 positioningthegasket 2 alreadypresentin the boiler and tighten...

Страница 16: ...xternal pipe must be fitted on the adaptor until it stops 1 N B to encourage the removal of possible condensate forming in the exhaust pipe tilt the pipes towards the boiler with a minimum slope of 1...

Страница 17: ...ed inside buildings in 23 or B53 mode in this case all technical rules and national and local regulations in force must be complied with type B open chamber boilers must not be installed in places whe...

Страница 18: ...non treated water To prevent corrosion the water system s PH should be between 6 5 and 8 5 Check the maximum content of chlorides which should be less than 250 mg l N B for quantities and methods of u...

Страница 19: ...ble to the system Head kPa A B Head available with by pass closed B Head available with by pass open C D Power absorbed by the pump with by pass open dotted area D Power absorbed by the pump with by p...

Страница 20: ...ty the entire system Moreover the version with filter preserves the functioning characteristics of the boiler thanks to its inspectionable filter Polyphosphate dispenser kit on request The polyphospha...

Страница 21: ...check that the air intake flue exhaust terminals if fitted are not blocked If temporary shutdown of the boiler is required proceed as follows a drain the heating system if antifreeze is not used b shu...

Страница 22: ...perating mode This function is always active and combined with the Solar ignition delay with time set above 0 seconds it manages the ignition of the boiler according to the domestic hot water inlet te...

Страница 23: ...e on and off again the 5 attempts are re acquired 10 Insufficient system pressure Water pressure inside the central heating circuit that is sufficient to guarantee the correct operation of the boiler...

Страница 24: ...ment it is only possible to control the system by means of the control panel of the boiler itself Check operation of the Wireless CAR checkthebatterycharge refertotherelative instructions booklet 59 M...

Страница 25: ...ler restarts without having to be reset 98 Block maximum no of software errors The maximum number of software errors possible has been reached Press the Reset button 1 99 General block A boiler anomal...

Страница 26: ...osed 2 10 ANTI FREEZE PROTECTION The Victrix Maior 28 35 TT 1 ErP series boiler has an anti freeze function that switches the burner on automatically when the temperature falls below 4 C standard prot...

Страница 27: ...commission the boiler ensure that the type of gas used corresponds to the boiler settings the type of gas appears on the display on first electrical power supply or by checking the relative parameter...

Страница 28: ...ow probe B2 Domestic hot water probe B4 External probe optional B5 Return probe B6 Domestic hot water flow meter B9 Domestic hot water inlet probe B10 Flue probe B24 Safety flow probe E3 Ignition and...

Страница 29: ...closed and also the functionality of the pump Drain trap clogged This may be caused by dirt or combustion products deposited inside Check that there are no residues of material blocking the flow of co...

Страница 30: ...o clock position Fig 3 5 and press the Reset button for about 8 seconds until the chimney sweep function is activated then press the summer winter button within 3 seconds Nominalheatoutput with the f...

Страница 31: ...3 seconds 3 9 Once the function is active the boiler sequential ly carries out the procedures required to calibrate the appliance with the nominal intermediate and minimum heat output values At this...

Страница 32: ...fgas parameter G and by restoring it according to the actual operating conditions wait for approximately 10 seconds between the gas change and the when it is restored 3 13 The restored values will be...

Страница 33: ...odel 6 Do not use on this boiler model 7 Do not use on this boiler model 0 7 1 P4 Relay 2 optional The boiler is set up for functioning with the relay P C B optional which can be configured 0 Off 1 Ge...

Страница 34: ...hanging the operating mode in order to quickly and comfortably satisfy an additional request for domestic hot water 0 100 seconds step 10 sec 2 t5 Central heating ignitions timer The boiler has electr...

Страница 35: ...ised value F0 Equivalent length flue Defines the length of the flue see par 3 11 0 2 0 F1 Not used on this boiler model In the event of an alteration anomaly E72 appears and fast calibration is requir...

Страница 36: ...the sealed chamber Check contents of the condensate drain trap Check that there are no residues of material clogging the condensate passage also check that the entire condensate drainage circuit is cl...

Страница 37: ...o screws a 2 Press the hooks inwards which block the lower grid b 3 remove the grid b Front panel Fig 3 15b 4 Open the protection door e1 pulling it towards you 5 Remove the cover caps c and loosen sc...

Страница 38: ...STALLER USER MAINTENANCE TECHNICIAN Ref X Control panel Fig 3 15d 9 Press the hooks on the side of the control panel i 10 Tilt the control panel i towards you Sides Fig 3 15e 11 Loosen screws k of sid...

Страница 39: ...2 1 09 0 80 9 0 7740 28 0 98 0 72 8 0 6880 24 0 87 0 64 7 0 6020 19 0 76 0 56 6 0 5160 15 0 65 0 48 5 0 4300 10 0 54 0 40 4 0 3440 6 0 44 0 32 3 0 2580 4 0 33 0 24 2 8 2408 1 0 30 0 22 Victrix Maior 3...

Страница 40: ...25 Flue temperature at nominal output C 51 52 Flue temperature at minimum output C 45 45 Victrix Maior 35 TT 1 ErP Gas nozzle diameter mm 6 15 6 15 Flue flow rate at nominal heat output kg h 55 56 Flu...

Страница 41: ...loss at flue with burner On Off 80 60 C 0 02 2 00 0 01 2 00 Central heating circuit max operating pressure bar 3 3 Maximum heating temperature C 90 90 Adjustable heating temperature max operation fie...

Страница 42: ...N Serial Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn max CH maximum heat i...

Страница 43: ...means 60 C on return and 80 C on flow Low temperature mode for condensation Boilers means 30 C for low temperature boilers 37 C and for other appliances 50 C of return tempera ture Model s Victrix Mai...

Страница 44: ...tion AFC 17 GJ Seasonal space heating energy efficiency s 93 Water heating energy efficiency wh 85 Parameter value Annual energy consumption for the heat ing function QHE 58 4 GJ Annual electricity co...

Страница 45: ...fiche of boiler Supplementary heat pump From fiche of heat pump Solar contribution and Supplementary heat pump Select smaller value Boiler and supplementary heat pump installed with low temperature he...

Страница 46: ...om fiche of heat pump The energy efficiency of the package of products provided far in this fiche may not correspond to its actual energy efficiency once installed in a building as the efficiency is i...

Страница 47: ...contribution From fiche of solar device 1 I 2 1 1 x I 10 x II III I Auxiliary electricity 3 G F E D C B A A A A 27 27 27 28 27 27 27 28 30 30 30 32 33 34 35 36 36 37 38 40 39 50 55 60 65 75 80 85 100...

Страница 48: ...ing energy efficiency under colder and warmer climate conditions Colder 0 2 x Warmer 0 4 x Declared load profile Solar contribution From fiche of solar device 1 ___ 2 1 1 x ___ 10 x ___ ____ ____ Auxi...

Страница 49: ...49...

Страница 50: ...50...

Страница 51: ...51...

Страница 52: ...mmergas com Immergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 038659ENG rev ST 001862 004 07...

Отзывы: