27
3-1
INS
TALLER
US
ER
MAINTEN
AN
CE TECHNI
CI
AN
Key:
1 - Gas valve
2 - Water inlet filter
*
3 - Domestic hot water flow meter
4 - Domestic hot water flow rate adjuster
5 - Domestic hot water probe
6 - System filling valve
7 - DHW heat exchanger
8 - System expansion vessel
9
- Condensation module
1
0
- Air / gas mixer
11 - Fan
12 - Ignition / detection electrode
13 - Air sample point
14 - Flue sample point
15 - Flue probe
16 - Manual vent valve
17 - Flow probe
18 - Safety flow probe
1
9
- Return probe
2
0
- Vent valve
21 - Boiler circulator pump
22 - System pressure switch
23 - Three-way valve (motorised)
24 - By-pass
25 - System draining valve
26 - D.H.W. inlet probe
27 - Condensate drain trap
28 - 3 bar safety valve
2
9
- 3 bar safety valve drain fitting signal
*
=
Attention:
check the presence and cleanli-
ness of the water inlet filter, which
guarantees the efficiency of the boiler
G - Gas supply
AC - Domestic hot water outlet
AF - Domestic cold water inlet
SC - Condensate drain
M - System flow
R - System return
3
BOILER COMMISSIONING
(
INITIAL CHECK
)
To commission the boiler:
- ensure that the type of gas used corresponds to
the boiler settings (the type of gas appears on
the display on first electrical power supply, or
by checking the relative parameter “G”);
- check connection to a 230V-50Hz power
mains, correct L-N polarity and the earthing
connection;
- make sure the central heating system is filled
with water and that the pressure gauge indicates
a pressure of 1-1.2 bar.
- switch the boiler on and check correct ignition;
- check the CO
2
flow rate in the flue:
- maximum (100%)
- intermediate (50%)
- minimum (0%)
the values must comply with what is indicated
in the relative tables (Fig. 3-14);
- check activation of the safety device in the event
of no gas, as well as the relative activation time;
- check the intervention of the main switch
located upstream of the boiler and in the boiler;
- check that the intake and/or exhaust terminals
are not blocked;
- ensure activation of all adjustment devices;
- check the production of domestic hot water;
- check sealing efficiency of water circuits;
- check ventilation and/or aeration of the instal-
lation room where provided.
If even only a single safety check offers a negative
result, do not commission the system.