Combustion products exhaust of natural 

draught or fan assisted appliances in open-top 

closed environments.

 In spaces closed on all 

sides with open tops (ventilation pits, court-

yards etc.), direct combustion product exhaust 

is allowed for natural draught or fan assisted gas 

appliances with a heat input range from 4 to 35 

kW, provided the conditions as per the current 

technical standards are respected.

1.21 WATER TREATMENT SYSTEM 

FILLING.

As already mentioned in the previous para-

graphs, a treatment of the thermal and domestic 

system water is required, in compliance with the 

local standards in force.
The parameters that influence the duration and 

proper operation of the heat exchanger are the 

water's PH, hardness, conductivity, and oxygen, 

together with the system's processing residues 

(any welding residues), any oil present and cor-

rosion products that can, in turn, cause damage 

to the heat exchanger. 
In order to prevent this from happening, you are 

recommended to:

- Before installation on new systems as well as 

old ones, clean the system with clean water to 

eliminate solid residues contained therein.

- Clean the system with a chemical treatment:
  -  Clean the new system with a suitable cleaning 

device (for example Sentinel X300, Fernox 

Cleaner F3 or Jenaqua 300) combined with 

thorough washing.

  -  Clean the old system with a suitable cleaning 

device (for example Sentinel X400 or X800, 

Fernox Cleaner F3 or Jenaqua 400) combined 

with thorough washing.

- Check the maximum hardness and quantity 

of filling water referring to the graphics (Fig. 

1-27). If the contents and hardness of the water 

are below the indicated curve, no specific treat-

ment is required; otherwise, to limit the content 

of calcium carbonate, you must provide for 

water-filling treatment. 

- For filling, you are not allowed to use water 

softened with the use of ionic-exchange resins 

or distilled water.

- Should you be required to provide for water 

treatment, this should be carried out by 

completely desalinating the filling water. As 

opposed to the complete softening process, 

desalinating the water completely not only 

removes hardening agents (Ca, Mg), but also 

eliminates all other minerals to reduce water-

filling conductivity up to 10 microsiemens/

cm. Given its low conductivity, desalinated 

water does not only prevent the formation of 

lime scale, but also serves as protection against 

corrosion.

- Insert a suitable inhibitor / passivator (for 

example Sentinel X100, Fernot Protector F1, 

or Jenaqua 100); if required, also insert appro-

priate antifreeze (such as for example Sentinel 

X500, Fernox Alphi 11 or Jenaqua 500).

-  Check electrical conduction of the water, which 

should not be higher than 2000 

µ

s/cm in the 

case of treated water and lower than 600 

µ

s/cm 

in the case of non-treated water.

- To prevent corrosion, the water system's PH 

should be between 6.5 and 8.5.

- Check the maximum content of chlorides, 

which should be less than 250 mg/l.

N.B.:

 for quantities and methods of use of water-

treatment products, refer to the instructions 

provided by their manufacturer.

1.22 SYSTEM FILLING.

Once the boiler is connected, proceed with 

system filling via the filling cock (Fig. 1-29 and 

1-3). Filling is performed at low speed to ensure 

release of air bubbles in the water via the boiler 

and heating system vents.

The boiler has a built-in automatic venting valve 

on the circulator. 

Check if the cap is loose.

 Open the 

radiator vent valves.

Close radiator vent valves when only water 

escapes from them.

Close the filling cock when the boiler pressure 

gauge indicates approx. 1.2 bar. 

N.B.:

 during these operations, enable the au-

tomatic vent functions on the boiler (active on 

first ignition). 

1.23 CONDENSATE TRAP FILLING.

On first lighting of the boiler, flue gas may come 

out the condensate drain; after a few minutes’ 

operation check that this no longer occurs. This 

means that the drain trap is filled with conden-

sate to the correct level preventing the passage 

of flue gas.

1.24 GAS SYSTEM START-UP.

To start up the system, refer to the technical 

standard in force. 

In particular, for new gas systems:

-   open windows and doors;
-   avoid presence of sparks or open flames;
-   bleed all air from the pipelines;
-  check that the internal system is properly sealed 

according to the specifications set forth by 

technical regulations in force.

1.25 BOILER START UP 

(

IGNITION

)

.

To commission the boiler (the operations listed 

below must only be performed by a qualified firm 

and without any unauthorised persons):

-  check that the internal system is properly sealed 

according to the specifications set forth by 

technical regulations in force;

-  ensure that the type of gas used corresponds to 

the boiler settings (the type of gas appears on 

the display on first electrical supply voltage, or 

by checking the relative parameter “G”);

- check connection to a 230V-50Hz power 

mains, correct L-N polarity and earthing con-

nection;

- Check that there are external factors that may 

cause the formation of fuel pockets; 

-  switch the boiler on and check correct ignition;
- make sure that the gas flow rate and relevant 

pressure values comply with those given in the 

manual (Par. 3.22);

- ensure that the safety device intervenes in the 

event of gas supply failure and check the relative 

intervention time;

- check the intervention of the main switch 

located upstream from the boiler and in the 

boiler;

-  check that the intake and/or exhaust terminals 

(if fitted) are not blocked.

- Carry out the flue test and set the relative 

parameter "F0".

The boiler must not be started up even if only 

one of the checks should be negative.

Water hardness °F

Sys

tem w

at

er l

itr

es

N.B.:

 the graph refers to the 

entire life cycle of the system. 

Therefore, also consider sched-

uled and unscheduled mainte-

nance, which involves emptying 

and filling the said system.

Содержание Victrix Maior 28 TT 1 ErP

Страница 1: ...VICTRIX MAIOR 28 35 TT 1 ERP IE Instruction and recommendation booklet 1 038659ENG...

Страница 2: ......

Страница 3: ...onal limits established by the Law Installation and maintenance must be performed in compliance with the regulations in force according to the manufacturer s instructions and by an authorised company...

Страница 4: ...on recommendations 5 1 2 Main dimensions 6 1 3 Antifreeze protection 6 1 4 Boiler connection unit 7 1 5 Gas connection 7 1 6 Hydraulic connection 7 1 7 Electric connection 8 1 8 Remote controls and ro...

Страница 5: ...boilerforpossiblewater and flue removal connections Keep all flamma ble objects away from the appliance paper rags plastic polystyrene etc Do not place household appliances underneath the boiler as th...

Страница 6: ...ary with respect to the minimum temperature at which the system must be kept An aqueous solution must be made with potential pollution class of water 2 EN 1717 2002 or local regula tions in force Atte...

Страница 7: ...n compliance with the tech nical standards in force in order to protect the system and the appliance from deposits e g scale slurry or other hazardous deposits In order not to void the heat exchanger...

Страница 8: ...d assembly instructions contained in the acces sory kit On Off Immergas digital chrono thermostat The chrono thermostat allows set two room temperature value one for daytime comfort temperature and on...

Страница 9: ...e always operates when con nected regardless of the presence or type of room chrono thermostat used and can work in combi nation with Immergas chrono thermostats The correlation between system flow te...

Страница 10: ...ctor allowed corresponds to the resistance encountered with the maximum allowed pipe length for each type of Terminal Kit This information allows calculations to be made to verify the possibility of s...

Страница 11: ...Intake and Exhaust 16 3 m 2 5 Intake m 18 7 Exhaust m 4 9 m 7 7 Exhaust m 13 6 Concentric vertical intake exhaust terminal 60 100 Intake and Exhaust 9 m 1 4 Intake m 10 3 Exhaust m 2 7 m 4 3 Exhaust m...

Страница 12: ...s present in the kit positioning the relevant gaskets Engage the 90 80 bend with the male end smooth in the female end with lip seal of the 80 flange unit until it stops Introduce the gasket making it...

Страница 13: ...the circular projections down wards in contact with the boiler flange and tighten using the screws present in the kit Fit the 60 100 3 concentric terminal pipe with the male side smooth to the female...

Страница 14: ...cal length of 14 4 m including the terminal This configuration corresponds to a resistance factor of 100 In this case specific extensions must be requested Vertical kit with aluminium tile 80 125 Kit...

Страница 15: ...t Remove the flat flange present in the lateral hole with respect to the central one ac cording to needs and replace it with the flange 3 positioningthegasket 2 alreadypresentin the boiler and tighten...

Страница 16: ...xternal pipe must be fitted on the adaptor until it stops 1 N B to encourage the removal of possible condensate forming in the exhaust pipe tilt the pipes towards the boiler with a minimum slope of 1...

Страница 17: ...ed inside buildings in 23 or B53 mode in this case all technical rules and national and local regulations in force must be complied with type B open chamber boilers must not be installed in places whe...

Страница 18: ...non treated water To prevent corrosion the water system s PH should be between 6 5 and 8 5 Check the maximum content of chlorides which should be less than 250 mg l N B for quantities and methods of u...

Страница 19: ...ble to the system Head kPa A B Head available with by pass closed B Head available with by pass open C D Power absorbed by the pump with by pass open dotted area D Power absorbed by the pump with by p...

Страница 20: ...ty the entire system Moreover the version with filter preserves the functioning characteristics of the boiler thanks to its inspectionable filter Polyphosphate dispenser kit on request The polyphospha...

Страница 21: ...check that the air intake flue exhaust terminals if fitted are not blocked If temporary shutdown of the boiler is required proceed as follows a drain the heating system if antifreeze is not used b shu...

Страница 22: ...perating mode This function is always active and combined with the Solar ignition delay with time set above 0 seconds it manages the ignition of the boiler according to the domestic hot water inlet te...

Страница 23: ...e on and off again the 5 attempts are re acquired 10 Insufficient system pressure Water pressure inside the central heating circuit that is sufficient to guarantee the correct operation of the boiler...

Страница 24: ...ment it is only possible to control the system by means of the control panel of the boiler itself Check operation of the Wireless CAR checkthebatterycharge refertotherelative instructions booklet 59 M...

Страница 25: ...ler restarts without having to be reset 98 Block maximum no of software errors The maximum number of software errors possible has been reached Press the Reset button 1 99 General block A boiler anomal...

Страница 26: ...osed 2 10 ANTI FREEZE PROTECTION The Victrix Maior 28 35 TT 1 ErP series boiler has an anti freeze function that switches the burner on automatically when the temperature falls below 4 C standard prot...

Страница 27: ...commission the boiler ensure that the type of gas used corresponds to the boiler settings the type of gas appears on the display on first electrical power supply or by checking the relative parameter...

Страница 28: ...ow probe B2 Domestic hot water probe B4 External probe optional B5 Return probe B6 Domestic hot water flow meter B9 Domestic hot water inlet probe B10 Flue probe B24 Safety flow probe E3 Ignition and...

Страница 29: ...closed and also the functionality of the pump Drain trap clogged This may be caused by dirt or combustion products deposited inside Check that there are no residues of material blocking the flow of co...

Страница 30: ...o clock position Fig 3 5 and press the Reset button for about 8 seconds until the chimney sweep function is activated then press the summer winter button within 3 seconds Nominalheatoutput with the f...

Страница 31: ...3 seconds 3 9 Once the function is active the boiler sequential ly carries out the procedures required to calibrate the appliance with the nominal intermediate and minimum heat output values At this...

Страница 32: ...fgas parameter G and by restoring it according to the actual operating conditions wait for approximately 10 seconds between the gas change and the when it is restored 3 13 The restored values will be...

Страница 33: ...odel 6 Do not use on this boiler model 7 Do not use on this boiler model 0 7 1 P4 Relay 2 optional The boiler is set up for functioning with the relay P C B optional which can be configured 0 Off 1 Ge...

Страница 34: ...hanging the operating mode in order to quickly and comfortably satisfy an additional request for domestic hot water 0 100 seconds step 10 sec 2 t5 Central heating ignitions timer The boiler has electr...

Страница 35: ...ised value F0 Equivalent length flue Defines the length of the flue see par 3 11 0 2 0 F1 Not used on this boiler model In the event of an alteration anomaly E72 appears and fast calibration is requir...

Страница 36: ...the sealed chamber Check contents of the condensate drain trap Check that there are no residues of material clogging the condensate passage also check that the entire condensate drainage circuit is cl...

Страница 37: ...o screws a 2 Press the hooks inwards which block the lower grid b 3 remove the grid b Front panel Fig 3 15b 4 Open the protection door e1 pulling it towards you 5 Remove the cover caps c and loosen sc...

Страница 38: ...STALLER USER MAINTENANCE TECHNICIAN Ref X Control panel Fig 3 15d 9 Press the hooks on the side of the control panel i 10 Tilt the control panel i towards you Sides Fig 3 15e 11 Loosen screws k of sid...

Страница 39: ...2 1 09 0 80 9 0 7740 28 0 98 0 72 8 0 6880 24 0 87 0 64 7 0 6020 19 0 76 0 56 6 0 5160 15 0 65 0 48 5 0 4300 10 0 54 0 40 4 0 3440 6 0 44 0 32 3 0 2580 4 0 33 0 24 2 8 2408 1 0 30 0 22 Victrix Maior 3...

Страница 40: ...25 Flue temperature at nominal output C 51 52 Flue temperature at minimum output C 45 45 Victrix Maior 35 TT 1 ErP Gas nozzle diameter mm 6 15 6 15 Flue flow rate at nominal heat output kg h 55 56 Flu...

Страница 41: ...loss at flue with burner On Off 80 60 C 0 02 2 00 0 01 2 00 Central heating circuit max operating pressure bar 3 3 Maximum heating temperature C 90 90 Adjustable heating temperature max operation fie...

Страница 42: ...N Serial Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn max CH maximum heat i...

Страница 43: ...means 60 C on return and 80 C on flow Low temperature mode for condensation Boilers means 30 C for low temperature boilers 37 C and for other appliances 50 C of return tempera ture Model s Victrix Mai...

Страница 44: ...tion AFC 17 GJ Seasonal space heating energy efficiency s 93 Water heating energy efficiency wh 85 Parameter value Annual energy consumption for the heat ing function QHE 58 4 GJ Annual electricity co...

Страница 45: ...fiche of boiler Supplementary heat pump From fiche of heat pump Solar contribution and Supplementary heat pump Select smaller value Boiler and supplementary heat pump installed with low temperature he...

Страница 46: ...om fiche of heat pump The energy efficiency of the package of products provided far in this fiche may not correspond to its actual energy efficiency once installed in a building as the efficiency is i...

Страница 47: ...contribution From fiche of solar device 1 I 2 1 1 x I 10 x II III I Auxiliary electricity 3 G F E D C B A A A A 27 27 27 28 27 27 27 28 30 30 30 32 33 34 35 36 36 37 38 40 39 50 55 60 65 75 80 85 100...

Страница 48: ...ing energy efficiency under colder and warmer climate conditions Colder 0 2 x Warmer 0 4 x Declared load profile Solar contribution From fiche of solar device 1 ___ 2 1 1 x ___ 10 x ___ ____ ____ Auxi...

Страница 49: ...49...

Страница 50: ...50...

Страница 51: ...51...

Страница 52: ...mmergas com Immergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 038659ENG rev ST 001862 004 07...

Отзывы: