It allows the diversion of the water flow of the primary circuit of the CH system to the
DHW plate heat exchanger and vice versa.
It is powered by the integrated P.C.B.
Three-way valve
(M30)
(
kW X version optional
)
Cuts the power supply to the circuit transformer off (230V/24V)
in low voltage when the current absorbed exceeds 315mA. It is
inserted onto the integrated P.C.B.
Transformer fuse
230V / 24V
(F2)
315 mAT 250 V
delayed fuse
When the safety temperature is exceeded (100 °C) remove the
power supply to the main coils of the gas valve.
It is positioned on the flow pipe at the outlet of the primary heat
exchanger.
Safety thermostat
(E4)
Klixon thermostat
with normally
closed contact
Loads.
It is controlled by the integrated P.C.B. when burner ignition is requested.
It makes the ignition spark.
It is organised inside the sealed chamber in the area under the condensation module at
the side of the expansion vessel.
Igniter
(G2)
Allows the circulation of water in the primary circuit.
It is powered by the integrated P.C.B. with a DHW, CH or anti-freeze request.
Pump
(M1)
They cause an electric spark, on the contact of which the air-gas mix ignites.
One electrode is connected to the igniter G2 while the other electrode is connected to
earth.
Ignition electrodes
(E1)
It is always powered and enables functioning of the boiler only when the main switch is
positioned in
(summer)
or
(winter) (see integrated P.C.B. functioning).
Integrated P.C.B.
It is a 230V/24V transformer that powers the low voltage adjustment circuit. It is located
inside the sealed chamber in the lower left area.
Transformer
(T2)
It is powered by the integrated P.C.B. when burner ignition is necessary.
It is powered at network voltage rectified by means of a diode jumper (U1) contained
inside the gas valve connector.
Allows the passage of gas to the burner.
Gas valve (Y1)
(
main coils
)
When the condensation module safety temperature is exceeded (167
°C) remove the power supply to the main coils of the gas valve. It
is positioned on the condensation module.
Exchanger safety thermofuse
(E13)
Thermofuse
When the flue safety temperature is exceeded (115 °C) remove the
power supply to the main coils of the gas valve.
It is positioned on the condensation module.
Flue safety thermofuse
(E14)
Thermofuse