58
STV2I ed 11/09
VICTRIX 2 I Export
Technical Documentation
Technical Documentation
ERROR 15
Wiring configuration error
N.B.: This board can be used for instant type boilers (VICTRIX 26 2 I) or with
storage tank (VICTRIX X 12 - X 24 2 I). The board automatically recognises the
type of boiler by means of the relative wiring.
15
The board is configured as instant boiler.
(NO jumper between clamps 7-8 of connector X8).
No
For the VICTRIX 26 2 I boiler check there is NO PRESENCE of the
connection jumper between clamps 7-8 of the connector X8.
Yes
Replace the P.C.B.
ERROR 16
Fan anomaly
16
a
The wiring between the P.C.B. and fan is OK.
Check continuity of the cable on clamp 5 of connector X12.
No
Restore the electric connection/replace the wiring.
Yes
Replace the fan. If the anomaly persists, replace the P.C.B.
16
b
At least 24 VDC is present to clamps 3-1 of the connector X12.
No
Replace the P.C.B.
Yes
The wiring between the P.C.B. and fan is OK.
No
Restore the electric connection/replace the wiring.
Yes
Replace the fan. If the anomaly persists, replace the P.C.B.
16
c
The wiring between the P.C.B. and fan is OK.
Check continuity of the cable on clamp 4 of connector X12.
No
Restore the electric connection/replace the wiring.
Yes
Replace the fan. If the anomaly persists, replace the P.C.B.
ERROR 20
Parasite flame block
The detection electrode and the relative wiring are integral.
No
Check and/or replace detection electrode/replace wiring.
Yes
Replace the P.C.B.
ERROR 27
Insufficient circulation
The pump functions correctly.
N.B.: make sure that the pump functions at maximum speed.
No
See section B
Yes
Any CH system zone valve or cut-off cocks are open.
No
Restore circulation in the CH system by acting on the closed devices
and also check:
- the correct functioning of the boiler by-pass;
- the opening times of any zone valves;
- the correct functioning of any thermostatic valves.
Yes
The NTC flow probe is OK (10 kΩ at 25°C).
No
Replace NTC flow probe.
Yes
Check/clean/replace the main heat exchanger (condensation module). If the anomaly persists, replace the P.C.B.