56
STV2I ed 11/09
VICTRIX 2 I Export
Technical Documentation
Technical Documentation
ERROR 01
No ignition block
01
a
230 VAC are present on clamps 2-3 of connector X7.
No
Replace the P.C.B.
Yes
230 VAC are present at the ends of the igniter.
No
Replace wiring.
Yes
The cables between igniter and electrodes corresponds.
No
Restore the electric connection/replace the wiring.
Yes
The igniter makes the spark.
No
Replace the igniter.
Yes
Check the correct positioning and the correct distance of the ignition electrodes (
see air-gas circuit
) and replace them if necessary.
01
b
230 VAC are present on clamps 6-7 of connector X7.
N.B: measure the voltage within the safety time (8-10 s).
No
Replace the P.C.B.
Yes
The connector and relative wiring between gas valve and P.C.B.
are OK.
No
Restore the electric connection/replace the wiring.
Yes
The position and the distance of the ignition electrodes with respect
to the burner is OK
(see air-gas circuit).
No
Restore the position and distance of the ignition electrodes.
Yes
Replace the gas valve.
N.B.: before replacing the valve make sure that there is enough gas inlet dynamic pressure and that the gas valve is correctly calibrated.
01
c
The electrode detects a direct current of 6-8 µA during the burner
ignition phase.
No
Replace the detection electrode and/or relative wiring.
Check correct position and distance between electrode and burner.
Check that siphon and the condensate exhaust duct are not blocked.
Yes
There are no combustion products in the air intake pipe.
N.B.: check the absence of CO
2
or other combustion products in the
intake pipe.
No
Check the correct positioning of the terminals, of all joints and
gaskets, to prevent the recirculation of the combustion products inside
the pipes.
N.B.: the error 01 could appear after the visualizing of the error 38.
Yes
Replace the P.C.B.
ERROR 02
Over-heating safety thermostat block
02
a
The wiring between safety thermostat, flue safety thermofuse,
exchanger safety thermofuse and P.C.B. is OK.
No
Restore the electric connection/replace the wiring.
Yes
The flue safety thermofuse positioned to protect the flue extraction
elements is OK.
No
Replace the thermofuse positioned on the flue hood.
N.B.: The cause
of breakage (opening) of the fuse must be identified before switching
the boiler back on.
Yes
The exchanger safety thermofuse positioned to protect the conden-
sation module is OK.
No
Replace condensation module.
N.B.: The cause of breakage (opening) of
the fuse must be identified before switching the boiler back on.
Yes
The safety thermostat functions regularly (intervention temperature
higher than 100°C).
No
Replace the over-heating safety thermostat.
Yes
Replace the P.C.B.
Functioning anomalies.