19
UK
10.5.2 Standard display
►
Select [SELd] and define the standard unit of measurement
FLOW = display shows the current volumetric flow value in the standard unit of meas-
urement�
TOTL = display shows the current meter reading in the unit providing the highest ac-
curacy�
TEMP = the current medium temperature in °C is displayed�
►
Select [diS] and set the update rate and orientation of the display:
d1 = update of the measured values every 50 ms�
d2 = update of the measured values every 200 ms�
d3 = update of the measured values every 600 ms�
rd1, rd2, rd3 = display like d1, d2, d3; rotated by 180�
OFF = the display is switched off in the operating mode� The LEDs remain active
even if the display is deactivated� Error messages are displayed even if the display is
deactivated�
10.5.3 Measured value damping
► Select [dAP] and set the damping constant in seconds (τ value 63 %).
10.5.4 Error behaviour of the outputs
►
Select [FOU1] and set the value:
-On = Output 1 switches ON in case of a fault�
-OFF = Output 1 switches OFF in case of an error�
-OU = Output 1 switches irrespective of the fault as defined with the parameters�
►
Select [FOU2] and set the value:
1� Switching output:
-On = Output 2 switches ON in case of a fault�
-OFF = Output 2 switches OFF in case of a fault�
-OU = Output 2 switches irrespective of the fault as defined with the parameters�
2� Analogue output:
-On = The analogue signal goes to the upper fault value�
OFF = The analogue value goes to the lower fault value�
OU = The analogue signal corresponds to the measured value�
10.5.5 Setting of the standard pressure
►
Select [rEF�P] and set the requested standard pressure�
10.5.6 Setting of the standard temperature
►
Select [rEF�T] and set the requested standard temperature�