14
Explanation of the menu
ImPS
Pulse value (consumed quantity at which 1 pulse is delivered)
ImPR
Configuration of the output for consumed quantity monitoring:
YES (pulse signal), no (switching signal)
SP1 / rP1
Upper / lower limit value for the volumetric flow at which OUT1 switches
OU1
Output function for OUT1 (volumetric flow):
-Hno, Hnc, Fno, Fnc: switching signal for the limits
-ImP: consumed quantity monitoring (totaliser function)
OU2
Output function for OUT2 (volumetric flow or temperature):
-Hno, Hnc, Fno, Fnc: switching signal for the limits
-I (current signal 4���20 mA)
Input function for OUT2:
-In�D: input for external meter reset signal
SP2 / rP2
Upper / lower limit value at which OUT2 switches�
ASP / AEP
Analogue start point / analogue end point for volumetric flow or
temperature on OUT2
DIn2
Configuration of the input for external meter reset signal:
HIGH, +EDG, LOW, -EDG
EF
Extended functions / opening of menu level 2
HI / LO Maximum / minimum value memory for volumetric flow
FOU1 / FOU2 Behaviour of OUT1 / OUT2 in case of an internal fault:
OU, On, OFF
dAP Measured value damping: damping constant in seconds
rTo Counter reset: manual reset / time-controlled reset
diS Update rate and orientation of the display
Uni Standard unit of measurement for volumetric flow: Nl/min, Nm
3
/h, Nm/s
SELd Standard measured variable of the display: FLOW (volumetric flow value),
TEMP (medium temperature), TOTL (meter reading)
SEL2 Standard unit of measurement for evaluation by OUT2:
FLOW (volumetric flow) or TEMP (temperature)
rEF�P Standard pressure to which the measured and display values for volumet-
ric flow refer
rEF�T Standard temperature to which the measured and display values for
volumetric flow refer
LFC Low flow cut-off
rES Restoring the factory settings