10.2.3 Analogue output flow rate (OUT2)
►
Select [SEL2] and set FLOW�
►
Select [OU2 ] and set the analogue function: I (4���20 mA)�
►
Select [ASP2] and set the volumetric flow value at which the minimum current value is
provided�
►
Select [AEP2] and set the volumetric flow value at which the maximum current value
is provided�
10.3 Settings for consumed quantity monitoring
10.3.1 Quantity monitoring by pulse output (OUT1)
►
Select [OU1] and set ImP�
►
Select [ImPR] and set YES�
►
Select [ImPS] and set the volumetric flow quantity at which 1 pulse is provided�
10.3.2 Quantity monitoring by preset counter (OUT1)
►
Select [OU1] and set ImP�
►
Select [ImPR] and set no�
►
Select [ImPS] and set the volumetric flow quantity at which output 1 switches�
10.3.3 Manual counter reset
►
Select [rTo] and set rES�T�
> The counter is reset to zero�
10.3.4 Time-controlled counter reset
►
Select [rTo] and set the requested value (intervals of hours, days or weeks)�
> The counter is reset automatically with the value now set�
10.3.5 Deactivation of the counter reset
►
Select [rTo] and set OFF�
> The meter is only reset after overflow (= factory setting)�