UK
Operating instructions FX460
23
AVERAGE FILTER
Optional averaging or filter function to avoid display fluctuations with unstable frequencies� With the
EXPONENTIAL FILTER setting the device uses an exponential function� The time constant T (63 %)
corresponds to the number of the sampling cycles�
Example: With SAMPLING TIME = 0�1 s and EXPONENTIAL FILTER 2 (exponential filter, T (63 %) = 2 x
sampling time) 63 % of the jump height are reached after 0�2 s�
OFF
No averaging
CYCLE FILTER 2
Free-flowing averaging with 2 cycles
CYCLE FILTER 4
Free-flowing averaging with 4 cycles
CYCLE FILTER 8
Free-flowing averaging with 8 cycles
CYCLE FILTER 16
Free-flowing averaging with 16 cycles
EXPONENTIAL FILTER 2
Exponential filter, T (63 %) = 2 x sampling time
EXPONENTIAL FILTER 4
Exponential filter, T (63 %) = 4 x sampling time
EXPONENTIAL FILTER 8
Exponential filter, T (63 %) = 8 x sampling time
EXPONENTIAL FILTER 16
Exponential filter, T (63 %) = 16 x sampling time
FOR/REV DETECTION
With this parameter the detection of the direction of rotation is activated (input A, input B with a phase shift
of 90 °)�
NO
Detection of the direction of rotation off�
YES
Detection of the direction of rotation on�
9.4 Process Time mode
In this menu, operation can be defined as baking and processing time display
(reciprocal rotational speed)� Only input A is active� This menu is only displayed if
the corresponding OPERATIONAL MODE is selected in the GENERAL MENU�
DISPLAY FORMAT
With this parameter, the required display format can be selected� The decimal point is set automatically by
selecting the format�
SECONDS
Indication in seconds (max� 99999999)
MINUTES
Indication in minutes (max� 99999999)
MIN:SEC
Indication in minutes: seconds (max� 999999:59)
MIN�00
Indication in minutes and 1/100 minutes (max� 999999�99)
H:M:S
Indication in hours: minutes : seconds (max� 9999:59:59)
DISPLAY VALUE
Setting of the required value that is to be displayed with the following reference frequency�
1
Lowest value
1000
Default value
99999999
Highest value