Operating instructions FX460
32
BATCH COUNTER
The batch counter is the source�
(Only visible in BATCH / TOTAL MODE with INCREMENT BATCH,
DECREMENT BATCH or USE INPUTS ONLY being set)�
TOTAL COUNTER
The total counter is the source�
(Only visible in BATCH / TOTAL MODE with TOTAL COUNTER being
set)�
TOTAL TIMER
The total timer is the source�
(Only visible in TOTAL TIME MODE with YES being set)�
MODE 1
Switching condition for preselection 1� Output / display switch according to the following conditions:
¦RESULT¦≥¦PRES¦
The result of the display value is greater than or equal to the result of
preselection 1
With hysteresis 1 not equal to 0 the following switching condition
results:
Display value ≥ preselection 1 → ON
Display value < preselection 1 - hysteresis 1 → OFF
¦RESULT¦≤¦PRES¦
The result of the display value is smaller than or equal to the result of
preselection 1 (start-up delay recommended)
With hysteresis 1 not equal to 0 the following switching condition
results:
Display value ≤ preselection 1 → ON
Display value > preselection 1 + hysteresis 1 → OFF
¦RESULT|=|PRES¦
The result of the display value is equal to the result of preselection 1�
In combination with hysteresis a frequency band (presel/- ½
hysteresis) can be defined and monitored�
With hysteresis 1 not equal to 0 the following switching condition
results:
Display value > preselection 1 + ½ hysteresis 1 → OFF
Display value < preselection 1 - ½ hysteresis 1 → OFF
RESULT≥PRES
If the display value is greater than or equal to preselection 1, e�g�
overspeed
With hysteresis 1 not equal to 0 the following switching condition
results:
Display value ≥ preselection 1 → ON
Display value < preselection 1 - hysteresis 1 → OFF
RESULT≤PRES
If the display value is smaller than or equal to preselection 1, e�g�
underspeed (start-up delay recommended)
With hysteresis 1 not equal to 0 the following switching condition
results:
Display value ≤ preselection 1 → ON
Display value > preselection 1 + hysteresis 1 → OFF
RESULT=PRES
Display value equal to preselection 1� In combination with hysteresis 1
a frequency band (presel/- ½ hysteresis) can be defined and
monitored�
With hysteresis 1 not equal to 0 the following switching condition
results:
Display value > preselection 1 + ½ hysteresis 1 → OFF
Display value < preselection 1 - ½ hysteresis 1 → OFF