Operating instructions AX460
38
9.18 Display menu
Parameter changes are only active after quitting the menu selection�
The totalization depends on the selected operating mode
�
START DISPLAY
This parameter defines the start display after power-on of the device�
SINGLE
One-line display� The source has to be defined in SOURCE SINGLE�
DUAL
Two-line display� The sources have to be defined in SOURCE DUAL
TOP / DOWN�
LARGE
Large display (only if parameter LARGE DISPLAY is activated) The
source has to be defined in SOURCE LARGE�
QUICKSTART
Display with quick-start function� Only for DX20x2, DX20x3, DX20x5�
MINIMUM / MAXIMUM
Display of the actual / minimum / maximum values of input 1 and input
2�
DUAL WITH UNIT
Two-line display with units� The sources have to be defined in
SOURCE DUAL TOP / DOWN�
SOURCE SINGLE
This parameter defines the source for preselection for a one-line display�
INPUT 1
Source is input 1
INPUT 2
Source is input 2
LINKAGE 1 – 2
The source is the result of the linking of input 1 and input 2
INPUT 1 TOTAL
Source is input 1 with totalization
INPUT 2 TOTAL
Source is input 2 with totalization
LINKAGE TOTAL
The source is the result of the linking of input 1 and input 2 with
totalization
IO LINK VALUE 1
The PDout value 1 sent by the IO-Link master is the source for
preselection
IO LINK VALUE 2
The PDout value 2 sent by the IO-Link master is the source for
preselection
MINIMUM VALUE 1
Source is input 1
MAXIMUM VALUE 1
Source is input 1
MINIMUM VALUE 2
Source is input 2
MAXIMUM VALUE 2
Source is input 2
SOURCE DUAL TOP
This parameter defines the source for preselection for the first line of a two-line display�
INPUT 1
Source is input 1
INPUT 2
Source is input 2
LINKAGE 1 – 2
The source is the result of the linking of input 1 and input 2
INPUT 1 TOTAL
Source is input 1 with totalization
INPUT 2 TOTAL
Source is input 2 with totalization