Operating instructions AX460
30
INPUT 1 TOTAL
Source is input 1 with totalization
INPUT 2 TOTAL
Source is input 2 with totalization
LINKAGE TOTAL
The source is the result of the linking of input 1 and input 2 with
totalization
IO LINK VALUE 1
The PDout value 1 sent by the IO-Link master is the source for
preselection
IO LINK VALUE 2
The PDout value 2 sent by the IO-Link master is the source for
preselection
MINIMUM VALUE 1
Source is input 1
MAXIMUM VALUE 1
Source is input 1
MINIMUM VALUE 2
Source is input 2
MAXIMUM VALUE 2
Source is input 2
MODE 1
Switching condition for preselection 1� Output / display switch according to the following conditions:
¦RESULT¦≥¦PRES¦
The result of the display value is greater than or equal to the result of
preselection 1
With hysteresis 1 not equal to 0, the following switching condition
results:
Display value ≥ preselection 1 → ON
Display value < preselection 1 - hysteresis 1 → OFF
¦RESULT¦≤¦PRES¦
The result of display value is smaller or equal to the result of
Preselection 1 (start-up delay recommended)
With hysteresis 1 not equal to 0 the following switching condition
results:
Display value ≤ preselection 1 → ON
Display value > preselection 1 + hysteresis 1 → OFF
¦RESULT¦=¦PRES¦
The result of the display value is equal to the result of preselection 1�
In combination with hysteresis, a frequency band (presel/- ½
hysteresis) can be defined and monitored�
With hysteresis 1 not equal to 0 the following switching condition
results:
Display value > preselection 1 + ½ hysteresis 1 → OFF
Display value < preselection 1 - ½ hysteresis 1 → OFF
RESULT≥PRES
If the display value is greater than or equal to preselection 1, e�g�
overspeed
With hysteresis 1 not equal to 0 the following switching condition
results:
Display value ≥ preselection 1 → ON
Display value < preselection 1 - hysteresis 1 → OFF
RESULT≤PRES
If the display value is smaller than or equal to preselection 1, e�g�
underspeed (start-up delay recommended)
With hysteresis 1 not equal to 0 the following switching condition
results:
Display value ≤ preselection 1 → ON
Display value > preselection 1 + hysteresis 1 → OFF