Operating instructions AX460
23
1/h
gal/min
Pa
kPa
%
Edit Unit
With this parameter, a customer-specific unit with up to 16 digits can
be edited�
Open the "Edit Unit" menu with the [OK] button� Use the arrow keys to
change the unit� Keep the arrow key pressed for fast scrolling� Save
with [OK]� Quit the "Edit Unit" menu with [C]�
SAMPLING TIME (S)
The set value corresponds to the sampling interval� This interval defines the interval in seconds between
the samples of the analogue signal� This parameter has a direct influence on the response time of the
device�
0,001
Lowest value
0�01
Default value
60,000
Highest value
AVERAGE FILTER
Optional averaging to prevent display fluctuations�
OFF
No averaging
CYCLE FILTER 2
Free-flowing averaging with 2 cycles
CYCLE FILTER 4
Free-flowing averaging with 4 cycles
CYCLE FILTER 8
Free-flowing averaging with 8 cycles
CYCLE FILTER 16
Free-flowing averaging with 16 cycles
OFFSET
With this parameter, the zero point shift / tare of the input is set�
-99,999
Lowest value
0
Default value
+99,999
Highest value