5.3.2 Board ID(Communication ID) Setting
Board ID is the unique address to communicate with PC. There is 5 channel DIP switch on the upper left side
of the iCON100 board for board ID setting. Each DIP switch has assigned address value and the board ID is
calculated by the sum value of each switch
set to “
ON
” position.
Board ID can be set from
‘
0
’
to
‘
31
’
. The
default value of board ID is
’
0
’
(5 channel DIP switch is set to
‘
OFF
’
position). Refer to the example below.
Caution
Each Board ID on the same communication loop must be not duplicated. If the same Board IDs are on
the same loop, the communication error will occur.
Figure: Position of Board ID Setting Switch
Communication ID= 0
(Default)
Communication ID=14
(2+4+8 = 14)
Communication= ID
(1+16 = 17)
Figure:
Board ID
Setting Example
Board ID Setting Switches