iCON100/iCON100-SR QUICK INSTALLATION GUIDE
14
- Connect one wire from a Door Contact Sensor to Input #2
- Connect the other wire from the Door Contact Sensor to GND
Auxiliary Input Connection (Applied to Input #3, Input #4 and Input #5)
- Connect one wire from an Auxiliary Input Device to one of the Input #3, #4 and #5.
- Connect the other wire from the Auxiliary Input Device to GND
Figure: Input Devices Connection
2.2K Resistance Connection for ‘Cut Off Check’
To use
the ‘Cut Off Check’ function, you have to connect 2.2K resistance between Input wire
(ex. Orange) and
GND.
Firstly you choose to use ‘Cut Off Check’. Follow the process as
[F2 SETUP MENU] -
>”5. IN/OUT
DEFINE”
“21.CUT OFF CHECK”. For setting of output, follow the process as [F2 SETUP MENU]
-
>”5.
IN/OUT DEFINE”
“18. CUT OFF ALARM”.
Figure: 2.2K Resistance C
onnection for ‘Cut Off Check’
5.4.3 Output Connections
Door Lock (Power Fail Safe) Connection (Relay #1)
- Connect COM port of Relay #1 to DC+12V
- Connect NC port of Relay #1 to (+) wire of door lock device
- Connect GND port to (-) wire of door lock devices
Door Lock (Power Fail Secure) Connection (Relay #1)
- Connect COM port of Relay #1 to DC+12V
- Connect NO port of Relay #1 to (+) wire of door lock device
- Connect GND port to (-) wire of door lock devices