5: F
UNCTIONS
AND
S
ETTINGS
5-18
FC6A S
ERIES
MICROS
MART
U
SER
’
S
M
ANUAL
FC9Y-B1722
High-Speed Counter Operation
The high-speed counter turns on an external output or executes an interrupt program when the current value matches the preset
value (target value).
For how to configure the function to turn on an external output, see "Comparison Actions" on page 5-21.
All-in-One CPU module
■
Single-phase high-speed counter
Group 1, group 2, group 5, group 6 single-phase high-speed counter
The high-speed counter has three operation modes, the adding counter, the up/down selection reversible counter, and the dual-pulse
reversible counter.
The up/down selection reversible counter and the dual-pulse reversible counter which can count in both directions are supported.
These groups support 100 kHz maximum pulse input and are capable of counting in a range from 0 to 4,294,967,295 (32 bits).
When the current value and the preset value match or an overflow or underflow occurs, a comparison output turns on or an interrupt
program is executed.
These groups support resetting the current value by the reset special internal relay or external reset input. When the reset is executed, the
current value returns to the reset value specified by the special data registers. For the reset input details, see "Reset input" on page 5-28.
Group 3, group 4 single-phase high-speed counter
These groups only support the adding counter.
These groups support 5 kHz maximum pulse input and are capable of counting in a range from 0 to 4,294,967,295 (32 bits).
When the current value and the preset value match or an overflow or underflow occurs, an external output turns on or an interrupt program
is executed.
These groups only support the reset input via a special internal relay. When the reset is executed, the current value returns to the reset value
specified by the special data registers.
■
Two-phase high-speed counter
Group 1-2, group 5-6 two-phase high-speed counter
The two-phase high-speed counter counts by the phase difference between the A-phase and B-phase pulse input.
These groups support 50 kHz maximum pulse input and are capable of counting in a range from 0 to 4,294,967,295 (32 bits).
Even higher speed counting is possible by specifying 2-edge count or 4-edge count.
When the current value and the preset value match or an overflow or underflow occurs, an external output turns on or an interrupt program
is executed.
These groups support resetting the current value by the reset special internal relay or external reset input (Z-phase). When the reset is
executed, the current value returns to the reset value specified by the special data registers.
Counting Mode
Frequency
Reset Input
Adding counter
Group 2, 6: 100 kHz
—
Group 1: 100 kHz
I2
Group 5: 100 kHz
I5
Up/down selection
reversible counter
Group 1-2: 100 kHz
I2
Group 5-6: 100 kHz
I5
Dual-pulse reversible
counter
Group 1-2: 100 kHz
I2
Group 5-6: 100 kHz
I5
Counting Mode
Frequency
Reset Input
Adding counter
Group 3, 4: 5 kHz
—
Counting Mode
Frequency
Reset Input (Z-phase)
2-edge count
Group 1-2: 50 kHz
I2
Group 5-6: 50 kHz
I5
4-edge count
Group 1-2: 25 kHz
I2
Group 5-6: 25 kHz
I5
Содержание MICROSmart FC6A Series
Страница 1: ...B 1722 8 FC6A SERIES User s Manual...
Страница 12: ...TABLE OF CONTENTS Preface 11 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Страница 182: ...2 PRODUCT SPECIFICATIONS 2 152 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Страница 434: ...8 INSTRUCTIONS REFERENCE 8 18 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Страница 520: ...11 SD MEMORY CARD 11 54 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Страница 554: ...13 TROUBLESHOOTING 13 26 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Страница 567: ...FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722 A 13 APPENDIX ASCII Character Code Table...