5: F
UNCTIONS
AND
S
ETTINGS
5-16
FC6A S
ERIES
MICROS
MART
U
SER
’
S
M
ANUAL
FC9Y-B1722
High-speed Counter External Inputs
The maximum points of the single-phase high-speed counter and two-phase high speed counter are as follows.
Single-phase high-speed counter
All-in-One CPU module
*1 If I2 or I5 is not used as reset inputs, they can be used as normal inputs.
*2 If Group 1 and Group 5 are used as
Up/Down Selection Reversible Counter
, use I1 as the Group 1 input (up/down selection input) and use
I7 as the Group 5 input (up/down selection input).
*3 If Group 1 and Group 5 are used as
Dual-Pulse Reversible Counter
, use I1 as the Group 1 input (pulse input) and I7 as Group 5 input (pulse
input).
Plus CPU module
*1 Can be used only with the Plus 32-I/O type.
*2 If I2, I5 or I13 is not used as reset inputs, they can be used as normal inputs.
*3 If Group 1, Group 3, or Group 5 is used as
Up/Down Selection Reversible Counter
, I1 is used as the up/down selection input of Group 1,
I4 is used as the up/down selection input of Group 3, and I7 is used as the up/down selection input of Group 5, respectively.
*4 If Group 1, Group 3, or Group 5 is used as
Dual-Pulse Reversible Counter
, I1 is used as the pulse input of Group 1, I4 is used as the pulse
input of Group 3, and I7 is used as the pulse input of Group 5, respectively.
Two-phase high-speed counter
All-in-One CPU module
External inputs I0/I1 (Group 1-2) and I6/I7 (Group 5-6) can be used as two-phase high-speed counters.
External inputs I2 and I5 can be used as reset inputs for Group 1-2 and Group 5-6.
*1 If I2 or I5 is not used as reset inputs, they can be used as normal inputs.
Type
16-I/O type
24-I/O type
40-I/O type
Plus 16-I/O type
Plus 32-I/O type
Single-phase High-speed
Counter Points (maximum)
6
6
6
6
6
Two-phase High-speed
Counter Points (maximum)
2
2
2
3
3
Group
1
2
3
4
5
6
External Input
I2
I0
I1
I3
I4
I5
I6
I7
Adding Counter
Reset input
Pulse input
Pulse input
Pulse input
Pulse input
Reset input
Pulse input
Pulse input
Up/Down
Selection
Reversible
Counter
Reset input
Pulse input
Up/down
selection
input
—
—
Reset input
Pulse input
Up/down
selection
input
Dual-pulse
Reversible
Counter
Reset input
Pulse input
(up)
Pulse input
(down)
—
—
Reset input
Pulse input
(up)
Pulse input
(down)
Group
1
2
3
4
5
6
External Input
I2
I0
I1
I3
I4
I5
I6
I7
Adding Counter
Reset
input
Pulse input
Pulse input
Reset
input
Pulse input
Pulse input
Reset
input
Pulse input
Pulse input
Up/Down
Selection
Reversible
Counter
Reset input
Pulse input
Up/down
selection
input
Reset input
Pulse input
Up/down
selection
input
Reset input
Pulse input
Up/down
selection
input
Dual-pulse
Reversible
Counter
Reset input
Pulse input
(up)
Pulse input
(down)
Reset input
Pulse input
(up)
Pulse input
(down)
Reset input
Pulse input
(up)
Pulse input
(down)
Group
1
2
3
4
5
6
External Input
I2
I0
I1
I3
I4
I5
I6
I7
Two-phase
High-speed
Counter
Reset input
(Z-phase)
Pulse input
(A-phase)
Pulse input
(B-phase)
—
—
Reset input
(Z-phase)
Pulse input
(A-phase)
Pulse input
(B-phase)
Содержание MICROSmart FC6A Series
Страница 1: ...B 1722 8 FC6A SERIES User s Manual...
Страница 12: ...TABLE OF CONTENTS Preface 11 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Страница 182: ...2 PRODUCT SPECIFICATIONS 2 152 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Страница 434: ...8 INSTRUCTIONS REFERENCE 8 18 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Страница 520: ...11 SD MEMORY CARD 11 54 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Страница 554: ...13 TROUBLESHOOTING 13 26 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Страница 567: ...FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722 A 13 APPENDIX ASCII Character Code Table...