Set the parameters to match the communication format used by the computer or operator interface.
* Values not in parentheses are the default settings.
4.
Click
OK
.
This concludes configuring the maintenance communications settings.
Baud Rate (bps)
: 115200 bps (1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200)
Data Bits
: 7 (7 or 8)
Parity
: Even (None, Even, Odd)
Stop Bit
: 1 (1 or 2)
Receive Timeout
: 500 ms (10 ms to 2550 ms)
Slave Number
: 0 (0 to 31)
Slave numbers are specified by constants or data registers.
Type
Details
Constant
Set within the range of 0 to 31
Data Register
Store the slave numbers 0 to 31 in the following special data registers
Port 1: D8100
Port 2: D8102
Port 3: D8103
Содержание MICROSmart FC6A-C16K1CE
Страница 1: ...B 1730 2 FC6A SERIES All in One Type Communication Manual...
Страница 60: ...3 COMMUNICATION SETTINGS 3 22 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 76: ...4 MAINTENANCE COMMUNICATION 4 16 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 126: ...5 USER COMMUNICATION INSTRUCTIONS 5 50 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 158: ...6 MODBUS COMMUNICATION 6 32 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 200: ...8 J1939 COMMUNICATION 8 32 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 218: ...10 SEND E MAIL FUNCTION 10 16 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 252: ...INDEX 4 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730 INDEX...