Specify the auto ping function items and click
OK
.
The auto ping function is composed of the following items.
3.
In the
Remote Host List
dialog box, select the check box of the remote hosts to ping when auto ping executes.
4.
Click
Close
.
This concludes configuring the settings.
Item
Setting Value
Online Status:
Specify the internal relay that stores the results of the pings sent with the auto ping function. If an internal relay is
entered, the range of internal relays that will be used is displayed on the right side.
The internal relays are all turned off when auto ping function execution starts. After the ping is sent, they are
turned on when a response is received.
When M8187 (auto ping stop flag) is turned from off to on, or when the user program is changed and the auto ping
function is set from "Used" to "Not used", the internal relay on/off status immediately before that is kept.
When M8187 (auto ping stop flag) is turned from on to off, or when the user program is changed and the auto
ping function is set from "Not used" to "Used", the internal relays are all turned off.
There is no impact on the operation of the PING instruction.
Operation Status:
Specify the data register that stores the operation status of the ping sent with the auto ping function. If a data
register is entered, the range of data registers that will be used is displayed on the right side.
The operation status indicates the operation status (status code) and the error details (error code). The status
code is stored in the upper 12 bits and the error code is stored in the lower 4 bits.
For the status code details, see "Operation status" on page 3-20.
There is no impact on the operation of the PING instruction.
Retry:
Specify the retry count (0 to 5 times) of the ping sent with the auto ping function.
Ping Interval:
Specify the send interval (0 to 60,000 ms) of the pings sent with the auto ping function in 10 ms increments.
Auto Ping Interval:
Specify the interval (100 to 6,000,000 ms) until the next auto ping is executed after the auto ping was executed in
100 ms increments.
Содержание MICROSmart FC6A-C16K1CE
Страница 1: ...B 1730 2 FC6A SERIES All in One Type Communication Manual...
Страница 60: ...3 COMMUNICATION SETTINGS 3 22 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 76: ...4 MAINTENANCE COMMUNICATION 4 16 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 126: ...5 USER COMMUNICATION INSTRUCTIONS 5 50 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 158: ...6 MODBUS COMMUNICATION 6 32 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 200: ...8 J1939 COMMUNICATION 8 32 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 218: ...10 SEND E MAIL FUNCTION 10 16 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 252: ...INDEX 4 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730 INDEX...