7: D
ATA
L
INK
C
OMMUNICATION
7-8
FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
C
OMMUNICATION
M
ANUAL
FC9Y-B1730
5.
Click
OK
.
6.
Create the user program.
7.
Transfer the user program.
This concludes configuring the settings
.
Note:
When you use data link communication, you have to turn on the slave stations first before turning on the master station. If you turn on the
master station before turning on the slave stations, the master station cannot recognize the slave stations. If the master station cannot recognize
the slave stations, you have to initialize the data link. To initialize the data link, click
Initialize Data Link
in WindLDR or turn on special internal
relay M8007 in the user program.
1.
Select
Online
>
Monitor
>
Monitor
>
Start Monitor
.
WindLDR enters monitor mode.
2.
Select
Online
>
PLC
>
Initialize
>
Initialize Data Link
.
The slave stations are recognized by the master station.
If you cannot perform WindLDR maintenance communication, insert the following program into the master station's user
program.
Stop and then run the master station to have it recognize the slave stations.
When operation (RUN) starts, M8007 is turned on for a period of one scan, and the data link is initialized.
Data Link Slave Station
1.
From the WindLDR menu bar, select
Configuration
>
Comm. Ports
.
The
Function Area Settings
dialog box for Communication Ports appears.
2.
Click
Communication Mode
for the port to use and select
Data Link Slave
.
The
Data Link Slave Settings
dialog box appears.
M8120: Initialize pulse
M8007: Communication initialization flag
Содержание MICROSmart FC6A-C16K1CE
Страница 1: ...B 1730 2 FC6A SERIES All in One Type Communication Manual...
Страница 60: ...3 COMMUNICATION SETTINGS 3 22 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 76: ...4 MAINTENANCE COMMUNICATION 4 16 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 126: ...5 USER COMMUNICATION INSTRUCTIONS 5 50 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 158: ...6 MODBUS COMMUNICATION 6 32 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 200: ...8 J1939 COMMUNICATION 8 32 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 218: ...10 SEND E MAIL FUNCTION 10 16 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 252: ...INDEX 4 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730 INDEX...