FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
C
OMMUNICATION
M
ANUAL
FC9Y-B1730
7-5
7: D
ATA
L
INK
C
OMMUNICATION
Data Link Communication between Master and Slave Stations
The master station has 6 data registers assigned to transmit data to a slave station and 6 data registers assigned to receive data
from a slave station. The quantity of data registers for data link can be selected from 0 through 6 using WindLDR. The following
examples illustrate how data is exchanged between the master and slave stations when 2 or 6 data registers are used for data link
communication with each of 31 slave stations.
Example 1: Transmit Data 2 Words and Receive Data 2 Words
Example 2: Transmit Data 6 Words and Receive Data 6 Words
Note:
When using port 2 or port 3, the communication status and error are stored in the registers configured in
Function Area Settings
.
Master Station
D8069
Communication Error
D900 - D901
Transmit Data
D906 - D907
Receive Data
D8070
Communication Error
D912 - D913
Transmit Data
D918 - D919
Receive Data
D8071
Communication Error
D924 - D925
Transmit Data
D930 - D931
Receive Data
D8072
Communication Error
D936 - D937
Transmit Data
D942 - D943
Receive Data
D8098
Communication Error
D1248 - D1249
Transmit Data
D1254 - D1255
Receive Data
D8099
Communication Error
D1260 - D1261
Transmit Data
D1266 - D1267
Receive Data
Slave Stations
D8069
Communication Error
Slave Station 1
D900 - D901
Transmit Data
D906 - D907
Receive Data
D8069
Communication Error
Slave Station 2
D900 - D901
Transmit Data
D906 - D907
Receive Data
D8069
Communication Error
Slave Station 3
D900 - D901
Transmit Data
D906 - D907
Receive Data
D8069
Communication Error
Slave Station 4
D900 - D901
Transmit Data
D906 - D907
Receive Data
D8069
Communication Error
Slave Station 30
D900 - D901
Transmit Data
D906 - D907
Receive Data
D8069
Communication Error
Slave Station 31
D900 - D901
Transmit Data
D906 - D907
Receive Data
Master Station
D8069
Communication Error
D900 - D905
Transmit Data
D906 - D911
Receive Data
D8070
Communication Error
D912 - D917
Transmit Data
D918 - D923
Receive Data
D8071
Communication Error
D924 - D929
Transmit Data
D930 - D935
Receive Data
D8072
Communication Error
D936 - D941
Transmit Data
D942 - D947
Receive Data
D8098
Communication Error
D1248 - D1253
Transmit Data
D1254 - D1259
Receive Data
D8099
Communication Error
D1260 - D1265
Transmit Data
D1266 - D1271
Receive Data
Slave Stations
D8069
Communication Error
Slave Station 1
D900 - D905
Transmit Data
D906 - D911
Receive Data
D8069
Communication Error
Slave Station 2
D900 - D905
Transmit Data
D906 - D911
Receive Data
D8069
Communication Error
Slave Station 3
D900 - D905
Transmit Data
D906 - D911
Receive Data
D8069
Communication Error
Slave Station 4
D900 - D905
Transmit Data
D906 - D911
Receive Data
D8069
Communication Error
Slave Station 30
D900 - D905
Transmit Data
D906 - D911
Receive Data
D8069
Communication Error
Slave Station 31
D900 - D905
Transmit Data
D906 - D911
Receive Data
Содержание MICROSmart FC6A-C16K1CE
Страница 1: ...B 1730 2 FC6A SERIES All in One Type Communication Manual...
Страница 60: ...3 COMMUNICATION SETTINGS 3 22 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 76: ...4 MAINTENANCE COMMUNICATION 4 16 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 126: ...5 USER COMMUNICATION INSTRUCTIONS 5 50 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 158: ...6 MODBUS COMMUNICATION 6 32 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 200: ...8 J1939 COMMUNICATION 8 32 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 218: ...10 SEND E MAIL FUNCTION 10 16 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 252: ...INDEX 4 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730 INDEX...