1: G
ENERAL
I
NFORMATION
1-2
FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
C
OMMUNICATION
M
ANUAL
FC9Y-B1730
Communication Cartridge
The communication cartridges can only be used when connected to cartridge slots 1 and 2 of the CPU module.
This port can be used to communicate with RS232C/RS485 communication-compatible external devices such as computers,
operator interfaces, and printers. Maintenance communication, user communication, Modbus RTU communication (master/slave),
and data link communication (master station/slave station) are possible.
CAN Port
The CAN J1939 All-in-One Type can use this port to perform J1939 communication.
HMI-Ethernet Port
The HMI-Ethernet port can only be used when a CPU module and an HMI module are connected.
This port can be used to communicate with Ethernet communication-compatible external devices such as computers and operator
interfaces.
This port has eight connections that can be used with Ethernet communication. Each connection can be configured for
maintenance communication (server).
This port also supports the web server function and the send E-mail function.
Type No.
FC6A-PC1
FC6A-PC3
Electrical Characteristics
EIA RS232C
EIA RS485
Maximum Communication Speed
115,200 bps
115,200 bps
Communication Functions
Maintenance communication, user communication, Modbus communication, data link communication
Maximum Cable Length
5 m
200 m
Isolation between Internal Circuit
Not isolated
Not isolated
Cable
Recommended
Cable
Shielded multicore: 24 AWG
Shielded twisted-pair: 24 AWG
Communication Type
CAN bus communication
Communication Speed
250 kbps
Communication Functions
J1939 communication
Connector
FC6A-PMTE05PN02
Cable
SAE-J1939-11
: Shielded twisted-pair
SAE-J1939-15
: Unshielded twisted-pair
Maximum Cable Length
SAE-J1939-11
: 40 m, stub 1 m maximum
SAE-J1939-15
: 40 m, stub 3 m maximum
Terminating Resistance
120
Ω
(0.5 W or higher)
Isolation between Internal Circuit
Power supply:
Transformer isolated
Signal:
Galvanic isolation, photocoupler isolated
Communication Type
IEEE 802.3 compliant
Communication Speed
10BASE-T, 100BASE-TX
Number of Connections
8 maximum
Communication Mode
Maintenance Communication
Web Server Function
Yes
Web Data Storage
FROM
Web Data
Capacity
System Web Page
Used
Used
Not used
Not used
Web Page Editor
Used
Not used
Used
Not used
Area Available to User
2.5 MB
4.5 MB
3.0 MB
5.0 MB
Send E-mail Function
Yes
Connector
RJ45
Cable
CAT 5. STP or higher
Maximum Cable Length
100 m
Isolation between Internal Circuit
Pulse transformer isolated
•
When accessing the FC6A Series MicroSmart over the Internet, adequate security measures for the network to prevent
unauthorized access are required. Be sure to consult your network administrator or Internet service provider. IDEC bears
no responsibility for damages or problems caused due to security in Ethernet communication.
•
Restrict the access to FC6A Series MicroSmart with IP addresses and ports by using appropriate measures such as the
firewall.
Caution
Содержание MICROSmart FC6A-C16K1CE
Страница 1: ...B 1730 2 FC6A SERIES All in One Type Communication Manual...
Страница 60: ...3 COMMUNICATION SETTINGS 3 22 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 76: ...4 MAINTENANCE COMMUNICATION 4 16 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 126: ...5 USER COMMUNICATION INSTRUCTIONS 5 50 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 158: ...6 MODBUS COMMUNICATION 6 32 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 200: ...8 J1939 COMMUNICATION 8 32 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 218: ...10 SEND E MAIL FUNCTION 10 16 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 252: ...INDEX 4 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730 INDEX...