Modbus TCP Server
When the FC6A Series MicroSmart is configured as the Modbus TCP server, Modbus TCP client devices can read/write data to the
FC6A Series MicroSmart. When the FC6A Series MicroSmart receives a valid request from a Modbus TCP client device, the data is
read or written according to the request received. The communication data received from Modbus TCP clients is processed at the
END processing of the user program.
Modbus TCP Server Specifications
*1 The number when all eight connections are set to Modbus TCP server.
Map of Slave Addresses for the Modbus TCP Server
Modbus TCP client can access the Modbus devices (Coil, Input Relay, Input Register, and Holding Register) of Modbus server to
read or write the device data (I, Q, M, R, T, C, and D) of FC6A Series MicroSmart. Refer to the following table to configure the
Modbus TCP clients.
*1 Slave addresses in communication are 4-digit values used in the address portion of the communication frame. Subtract 1 from the lower 5 digits
of the slave address and store that value in hexadecimal. For details, see "Modbus RTU Slave Communication" on page 6-8.
*2 Access within the device range for the FC6A Series MicroSmart type used.
Parameter
Modbus TCP Server
Slave Number
Ignored
Response Time
1.5 ms
Number of Clients that can Access Simultaneously
8 (1 client per 1 connection)
Port Number
502 (can be changed between 0 and 65535)
Supported Function Code
01 Read Coil Status
02 Read Input Status
03 Read Holding Registers
04 Read Input Registers
05 Force Single Coil
06 Preset Single Register
15 Force Multiple oils
16 Preset Multiple Registers
Modbus Device Name
Slave Addresses
Slave Addresses in
Communication
FC6A Series MicroSmart Device
Applicable
Function Code
Coil
(000000 and above)
000001 - 000504
0000 - 01F7
Q0 - Q627
1,5,15
000701 - 000956
02BC - 03BB
R000 - R255
001001 - 003048
03E8 - 0BE7
M0000 - M2557
003049 - 007400
0BE8 - 1CE7
M2560 - M7997
009001 - 009256
2328 - 2427
M8000 - M8317
011001 - 017000
2AF8 - 4267
M10000 - M17497
Input Relay
(100000 and above)
100001 - 100504
0000 - 01F7
I0 - I627
2
101001 - 101256
03E8 - 04E7
T000 - T255 (timer contact)
101501 - 101756
05DC - 06DB
C000 - C255 (counter contact)
102001 - 102768
07D0 - 0ACF
T256 - T1023 (timer contact)
104001 - 104256
0FA0 - 109F
C256 - C511 (counter contact)
Input Register
(300000 and above)
300001 - 300256
0000 - 00FF
T000 - T255 (timer current value)
4
300501 - 300756
01F4 - 02F3
C000 - C255 (counter current value)
302001 - 302768
07D0 - 0ACF
T256 - T1023 (timer current value)
304001 - 304256
0AF0 - 10A0
C256 - C511 (counter current value)
Holding Register
(400000 and above)
400001 - 408000
0000 - 1F3F
D0000 - D7999
3,6,16
408001 - 408500
1F40 - 2133
D8000 - D8499
409001 - 409256
2328 - 2427
T000 - T255 (timer preset value)
3
409501 - 409756
251C - 261B
C000 - C255 (counter preset value)
410001 - 456000
2710 - DABF
D10000 - D55999
3,6,16
462001 - 462768
F230 - F52F
T256 - T1023 (timer preset value)
3
464001 - 464256
FA00 - FAFF
C256 - C511 (counter preset value)
Содержание MICROSmart FC6A-C16K1CE
Страница 1: ...B 1730 2 FC6A SERIES All in One Type Communication Manual...
Страница 60: ...3 COMMUNICATION SETTINGS 3 22 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 76: ...4 MAINTENANCE COMMUNICATION 4 16 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 126: ...5 USER COMMUNICATION INSTRUCTIONS 5 50 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 158: ...6 MODBUS COMMUNICATION 6 32 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 200: ...8 J1939 COMMUNICATION 8 32 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 218: ...10 SEND E MAIL FUNCTION 10 16 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 252: ...INDEX 4 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730 INDEX...