MICRO/I Hardware Manual
1-51
3 HG4G/3G, HG2G-5F
1
M
ain
U
nit S
pe
cific
atio
ns
3.7 Installation
●
Operating Environment
For designed performance and safety of the HG4G/3G, HG2G-5F, do not install the HG4G/3G, HG2G-5F in the
following environments:
• Where dust, briny air, or iron powder exist.
• Where oil or chemical splashes for a long time.
• Where space is filled with oil mist.
• Where direct sunlight falls on the main unit.
• Where strong ultraviolet rays fall on the main unit.
• Where corrosive or combustible gasses exist.
• Where shocks or vibrations are transmitted.
• Where condensation occurs due to rapid temperature change.
• Where high-voltage or arc-generating equipment (electromagnetic contactors or circuit protectors) exists in close
proximity.
●
Ambient Temperature
• Allow sufficient space for ventilation, and install the equipment away from heat sources.
• Allow at least 100mm between the HG4G/3G, HG2G-5F and walls or other equipment.
• Do not install the HG4G/3G, HG2G-5F where the ambient temperature exceeds the rated operating ambient
temperature range. When mounting the HG4G/3G, HG2G-5F in such locations, provide a forced air-cooling fan or
air-conditioner to keep the ambient temperature within the rated temperature range.
• The HG4G/3G, HG2G-5F is designed to install on a vertical plane so that natural air-cooling is provided. If you
install it using any other orientation, use forced-air cooling, or lower the ambient operating temperature.
●
Installation
• Make a panel cut-out on the panel with the dimensions shown below.
Unit: mm
Model
A
B
Panel Thickness
HG4G
227.5
+2.0
0
301.5
+2.0
0
2.0 to 5.0
HG3G-A
200.0
+2.0
0
258.0
+2.0
0
2.0 to 5.0
HG3G-8
164.0
+2.0
0
219.0
+2.0
0
2.0 to 5.0
HG2G-5F
121.0
+2.0
0
153.0
+2.0
0
1.6 to 5.0
B
A