3 HG4G/3G, HG2G-5F
1-46
MICRO/I Hardware Manual
■
Performance Specifications
■
EMC Specifications
Type Number
HG4G
HG3G-A
HG3G-8
HG2G-5F
Display
LCD Type
TFT color LCD (TN Type)
Display Colors
65,536 Colors
Effective Display Area
246.0 (W) ×
184.5 (H) mm
211.2 (W) ×
158.4 (H) mm
170.4 (W) ×
127.8 (H) mm
115.2 (W) ×
86.4 (H) mm
Display Resolution
800 (W) × 600 (H) dots
640 (W) × 480 (H) dots
View angle
Left/Right: 80°, Top: 80°, Bottom: 60°
Left/Right/Top/Bottom: 80°
Brightness of LCD only
550 cd/m
2
700 cd/m
2
600 cd/m
2
800 cd/m
2
Brightness Adjustment
48 levels
Backlight
LED
Backlight Life
Approx. 100,000 hours (The time until
brightness becomes 50% of the initial value)
Approx. 50,000 hours (The time until
brightness becomes 50% of the initial
value)
Touch
Panel
Switch Type
Analog Resistive Film
Operating Force
3N maximum 0.55 to 2.3 N
3N maximum
Multiple Operations
Impossible
Life
1,000,000 operations
User Memory
Approx. 12 MB
Backup Battery
Coin type lithium manganese dioxide battery CR2032
Guarantee Period: 1 Year (Ambient Operating Temperature at 25°C)
Recommended Replacement Span: Every 5 Years Ambient Operating Temperature at
25°C)
Backup Data
Calendar, Log Data, HMI Keep Relays, HMI Keep Registers
Buzzer output
Single tone (tone length is adjustable)
Degree of Protection
IP66 (IEC 60529)
TYPE 4X
TYPE 13
Weight (approx.)
2.1kg
1.65 kg
1.25 kg
0.65 kg
*1 Please be aware that small black and bright dots might show up on LCD Screen: it is not a failure or malfunction.
*2 The life of the LCD itself at an ambient temperature of 25°C. This is not a guaranteed value. The actual life depends on the
environment and conditions of use.
*3 It is a protection structure for the operating surface of HMI, which is attached to a panel. Although protection structure
suffices every test conditions, it does not guarantee to operate under all of the environmental condition. Protection structure
do not guarantee usage under long exposure to oil or usage of oil that is not prescribed in the document. Please test/check
beforehand to avoid trouble.
Radiated Emission
Class A: 10m
40dBµV/m quasi-peak (30M to 230MHz)
47dBµV/m quasi-peak (230M to 1GHz)
Electrostatic Discharge
Contact: ±6kV
Air: ±8kV
Electromagnetic Field
10V/m (80M to 1000MHz)
3V/m (1.4G to 2.0GHz)
1V/m (2.0G to 2.7GHz)
80% AM (1kHz)
Fast Transient/Burst
Power: ±2kV
Communication cable: ±1kV
Surge Immunity
±500V (b24V and 0V)
±1kV (b24V and FE, 0 and FE)
Conducted Radio
Frequency Immunity
3V (Power, Communication cable) (150k to 80MHz)