1 HG2J-7U
1-6
MICRO/I Hardware Manual
■
Performance Specifications
Display
LCD Type
TFT color LCD (TN Type)
Display Colors
65,536 Colors
Effective Display Area 154.08 (W) × 85.92 (H) mm
Display Resolution
800 (W) × 480 (H) dots
Dot pitch
0.1926 (W) x 0.179 (H) mm
View angle
Left/Right/Top: 80°, Bottom: 60°
Brightness of LCD only 500 cd/m
2
Brightness Adjustment 48 levels
Backlight
LED (white)
Backlight Life
Approx. 50,000 hours (The time until brightness becomes 50% of the initial value)
Touch
Panel
Switch Type
Projected Capacitive
Multiple Operations
Possible (2-point touch)
User Memory
Approx. 24 MB
Backup time of the real-time
clock (Ambient Operating
Temperature at 25°C)
Min. 20 days
Backup Data
Calendar, Log Data, HMI Keep Relays, HMI Keep Registers
Buzzer output
Single tone (tone length is adjustable)
Degree of Protection
Panel thickness is 1 mm or more and less than 1.6 mm: IP65F IEC 60529)
Panel thickness is 1.6 mm or more and 5 mm or less:
IP66F, IP67F (IEC 60529),
TYPE 4X (indoor use only),
TYPE 13
Weight (approx.)
500g
*1 Please be aware that small black and bright dots might show up on LCD Screen: it is not a failure or malfunction.
*2 The life of the LCD itself at an ambient temperature of 25°C. This is not a guaranteed value. The actual life depends on the
environment and conditions of use.
*3 It is a protection structure for the operating surface of HMI, which is attached to a panel. Although protection structure
suffices every test conditions, it does not guarantee to operate under all of the environmental condition. As for IP65F/IP66F/
IP67F oilproof structure, it suffices oilproof test conditions. Conditions are listed in the document that comes with Japanese
Industrial Standard JIS C 0920. Protection structure do not guarantee usage under long exposure to oil or usage of oil that
is not prescribed in the document. Please test/check beforehand to avoid trouble. IP ratings are not applicable to UL
certification.
*4 If the power interruption period exceeds the Backup time of the real-time clock, the error message "Initialize clock data" will
be displayed when the power is turned on, and the clock data will be initialized to 00:00:00 on January 1, 2000.