Functions
74
HR9Z-B2200 8/2020
Automatic Start
With automatic start, the start input is permanently active. This can be achieved by bridging the
start input or providing an external power supply. When the safety-related input is activated, the
safety-related outputs are activated within a maximum of 100 ms (activation delay).
The following timing diagram illustrates the automatic start:
1 Activation delay (100 ms): maximum time between activation of safety-related input and activation of
safety-related output
2 Response time (20 ms): maximum time between deactivation of safety-related input and deactivation of
safety-related output
3 Recovery time (200 ms): time that must pass before the safety-related input can be activated again
The timing diagram exemplifies the timing using one safety-related input and one safety-related
output. The same logic applies in the case of multiple safety-related inputs and/or safety-related
outputs.
Содержание HR6S-DN
Страница 1: ...http www idec com HR6S DN Safety Module Original instructions HR9Z B2200...
Страница 8: ...8 HR9Z B2200 8 2020...
Страница 14: ...14 HR9Z B2200 8 2020...
Страница 20: ...Introduction 20 HR9Z B2200 8 2020...
Страница 56: ...Installation 56 HR9Z B2200 8 2020...
Страница 60: ...Functions 60 HR9Z B2200 8 2020 Wiring of the inputs for Emergency Stop Wiring of the inputs for guards...
Страница 64: ...Functions 64 HR9Z B2200 8 2020 Wiring of the inputs for coded magnetic switches...
Страница 66: ...Functions 66 HR9Z B2200 8 2020 Wiring of the inputs for coded magnetic switches...
Страница 69: ...Functions HR9Z B2200 8 2020 69 Wiring of the inputs for sensors devices with two PNP outputs...
Страница 72: ...Functions 72 HR9Z B2200 8 2020 Wiring of the inputs for sensors devices with OSSD outputs...
Страница 98: ...Accessories Service Maintenance and Disposal 98 HR9Z B2200 8 2020...