
Technical Data
28
HR9Z-B2200 8/2020
Safety-Related Outputs
Additional Non-Safety-Related Outputs
Characteristic
Value
Number of relay contacts, Normally Open, instantaneous 3
Number of relay contacts, Normally Closed,
instantaneous
1
Maximum short circuit current IK
1 kA
Maximum continuous current, Normally Open relay
contacts
6 A
Maximum continuous current, Normally Closed relay
contacts
3 A
Maximum total thermal current ∑I
th
12 A
Minimum current
10 mA
Minimum voltage
5 V
Utilization category as per UL 60947-5-1
B300 and R300 for Normally Open contacts
D300 and R300 for Normally Closed contacts
Utilization category as per IEC 60947-4-1 and IEC 60947-
5-1)
AC-1: 250 V
AC-15: 250 V
DC-1: 24 V
DC-13: 24 V
Maximum current, normally open relay contacts
AC-1: 5 A
AC-15: 3 A
DC-1: 5 A
DC-13: 3 A
Maximum current, normally closed relay contacts
AC-1: 3 A
AC-15: 1 A
DC-1: 3 A
DC-13: 1 A
External fusing
10 A, category gG, for Normally Open
4 A, category gG, for Normally Closed
Characteristic
Value
Number of semiconductor pulsed outputs
1
Output voltage
24 VDC
Maximum current
20 mA
Содержание HR6S-DN
Страница 1: ...http www idec com HR6S DN Safety Module Original instructions HR9Z B2200...
Страница 8: ...8 HR9Z B2200 8 2020...
Страница 14: ...14 HR9Z B2200 8 2020...
Страница 20: ...Introduction 20 HR9Z B2200 8 2020...
Страница 56: ...Installation 56 HR9Z B2200 8 2020...
Страница 60: ...Functions 60 HR9Z B2200 8 2020 Wiring of the inputs for Emergency Stop Wiring of the inputs for guards...
Страница 64: ...Functions 64 HR9Z B2200 8 2020 Wiring of the inputs for coded magnetic switches...
Страница 66: ...Functions 66 HR9Z B2200 8 2020 Wiring of the inputs for coded magnetic switches...
Страница 69: ...Functions HR9Z B2200 8 2020 69 Wiring of the inputs for sensors devices with two PNP outputs...
Страница 72: ...Functions 72 HR9Z B2200 8 2020 Wiring of the inputs for sensors devices with OSSD outputs...
Страница 98: ...Accessories Service Maintenance and Disposal 98 HR9Z B2200 8 2020...