Electrical Installation
General Information
Wiring of the device depends on the safety-related function to be implemented. Before wiring the
device, engineer the safety-related function, perform a risk assessment with regard to your
machine/process, and determine the suitability of the device as well as the connected equipment.
You can wire the device with the terminal blocks in the device or you can remove the terminal
blocks. For the latter, pull the terminal blocks out of the device, connect the individual terminals and
push the terminal blocks back into the device.
Use 75 °C (167 °F) copper conductors to wire the device.
Wire Cross Sections, Stripping Lengths, and Tightening Torques
DANGER
FIRE, ELECTRIC SHOCK OR ARC FLASH
Disconnect all power from all equipment of your machine/process prior to electrical installation
of the device.
Confirm the absence of power using a properly rated voltage sensing device.
Place a "Do Not Turn On" or equivalent hazard label on all power switches and lock them in
the non-energized position.
Failure to follow these instructions will result in death or serious injury.
Characteristic
Value
Stripping length for Push-in terminals
12 mm (0.47 in)
Stripping length for screw terminals
7 ... 8 mm (0.28 ... 0.31 in)
Wire cross section, single wire without wire ferrule
(1)
0.2 ... 2.5 mm
2
(24 ... 12 AWG)
Wire cross section, single wire with wire ferrule
0.25 ... 2.5 mm
2
(24 ... 12 AWG)
Wire cross section, two wires without wire ferrule
(1)
0.2 ... 1.5 mm
2
(24 ... 16 AWG)
Wire cross section, two wires with uninsulated wire
ferrule
0.25 ... 1 mm
2
(24 ... 18 AWG)
Wire cross section, two wires with insulated wire
ferrule
0.5 ... 1.5 mm
2
(20 ... 16 AWG)
Tightening torque for screw terminals
0.5 ... 0.6 N m (4.4 ... 5.3 lb in)
(1) Stranded or solid
Содержание HR6S-DN
Страница 1: ...http www idec com HR6S DN Safety Module Original instructions HR9Z B2200...
Страница 8: ...8 HR9Z B2200 8 2020...
Страница 14: ...14 HR9Z B2200 8 2020...
Страница 20: ...Introduction 20 HR9Z B2200 8 2020...
Страница 56: ...Installation 56 HR9Z B2200 8 2020...
Страница 60: ...Functions 60 HR9Z B2200 8 2020 Wiring of the inputs for Emergency Stop Wiring of the inputs for guards...
Страница 64: ...Functions 64 HR9Z B2200 8 2020 Wiring of the inputs for coded magnetic switches...
Страница 66: ...Functions 66 HR9Z B2200 8 2020 Wiring of the inputs for coded magnetic switches...
Страница 69: ...Functions HR9Z B2200 8 2020 69 Wiring of the inputs for sensors devices with two PNP outputs...
Страница 72: ...Functions 72 HR9Z B2200 8 2020 Wiring of the inputs for sensors devices with OSSD outputs...
Страница 98: ...Accessories Service Maintenance and Disposal 98 HR9Z B2200 8 2020...