73 CONDENSATE TRAP REPLACEMENT
SERVICING
1.
Refer to Frame 60.
2.
Remove the boiler casing. Refer to
Frame 53.
3.
Remove the boiler sealing panel.
Refer to Frame 54.
4.
Remove the fan assembly. Refer to
Frame 55.
5.
Pull off the condensate trap from
the bottom panel and carefully
empty the contained water into a
receptacle.
6.
Pull off the trap from the bottom of
the boiler.
7.
Withdraw the trap from the boiler.
8.
Fit the new trap and re-assemble in
reverse order.
74 DHW THERMISTOR SENSOR REPLACEMENT
1.
Refer to Frame 60.
2.
Remove the boiler casing. Refer to
Frame 53.
3.
Swing the control panel down.
4.
Close the DHW inlet isolating
valve.
5.
Open the lowest DHW draw-off tap.
6.
Pull the electrical lead off the
sensor.
7.
Unscrew the sensor from the plate
heat exchanger.
8.
Fit the new sensor, using a suitable
jointing compound, and re-
assemble in reverse order.
SER
VICING