14
-
Installation & Servicing
INSTALLATION
14 VERTICAL ROOF FLUE KIT
Contents
•
Boiler a screws (x6)
•
Terminal
•
Locking Collar
•
Finishing plates (x2)
•
Bracket
RF
2498
Note: See Frame 19 for elbow equivalent lengths.
15 VERTICAL ROOF FLUE KIT - For longer flue lengths for the
W45 and W60
Contents
•
Boiler a screws (x6)
•
Increaser
•
Terminal
•
Locking Collars (x2)
•
Finishing plates (x2)
•
Bracket
RF
2499
Flue System
Part No. Max Flue Ext.
W45
W60
Vertical roof kit 80/125
158654
m
9.5
7.8
suitable for
W45 & W60
Pa
60
78
Vertical roof kit 100/150
158656
m
16
suitable for
W80
Pa
100
Achievable flue
length without
extensions
0.65
0.8
Note: See Frame 19 for elbow equivalent lengths.
Flue System
Part No. Max Flue Ext.
W45
W60
Vertical roof kit 100/150
158655
m
31.6
26
suitable for
W45 & W60
Pa
79
108
Achievable flue
length without
extensions
0.9
FLUE OUTLET