Installation & Servicing
FAULT FINDING
FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING
Code
Description
Action
E 17
Internal failure
Check wiring harnesses & connections
If wiring OK replace boiler control module
E 18
Flow temperature too high
Check no air in system or boiler
Check adequate flow of water through boiler
E 19
Return temperature too high
Check no air in system or boiler
Check adequate flow of water through boiler
E 25
Flow temperature rise too fast
Check no air in system or boiler
Check adequate flow of water through boiler
E 28
No tacho from fan
Check electrical connections to fan
If connections OK & fan rotates, replace fan
E 29
Tacho signal from fan does not reset to zero
Replace fan
E 30
Flow/return temperature differential too high
Check no air in system or boiler
Check adequate flow of water through boiler
E 31
Flow thermister short circuit
Check wiring
Disconnect terminals from thermistor & confirm
short circuit using meter
Replace thermister
E 32
Return thermistor short circuit
Check wiring
Disconnect terminals from thermister & confirm
short circuit using meter
Replace thermister
E 33
DHW thermistor short circuit
Check wiring
Disconnect terminals from thermister & confirm
short circuit using meter
Replace thermister
E 36
Flow thermistor open circuit
Check wiring
Disconnect terminals from thermister & confirm
open circuit using meter
Replace thermister
E 37
Return thermistor open circuit
Check wiring
Disconnect terminals from thermister & confirm
open circuit using meter
Replace thermister
E 38
Tank sensor open circuit
If not fitted check parameter 35 settings
Check wiring
Disconnect terminals from tank sensor & confirm
open circuit using meter
Replace tank sensor
E 44
Internal failure
Check wiring harnesses & connections
If wiring OK replace boiler control module
E 60
Error reading parameters
Replace boiler control module
E 61
Air pressure switch does not open (W80 only)
Check for blockages in air pressure switch
sensing pipes
Check air pressure switch & replace if necessary
E 65
Not enough fan driving force
Check supply voltage to fan
Replace fan
Boiler Control Module Error Codes Continued