Installation & Servicing
FAULT FINDING
FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING FAUL
T FINDING
Code
Description
Action
b 18
Flow temperature >95degC
Check no air in system or boiler
Check adequate flow of water through boiler
b 19
Return temperature >95degC
Check no air in system or boiler
Check adequate flow of water through boiler
b 24
Return temperature > Flow temperature for excessive time
Check no air in system or boiler
Check adequate flow of water through boiler
b 25
Flow temperature rise too fast
Check no air in system or boiler
Check adequate flow of water through boiler
b 26
Minimum water pressure switch not closed
Check no air in system or boiler
If sealed system check charge pressure
If open vent system check minimum head is 3m
Check wiring to water pressure switch
Check water pressure switch with meter & replace if necessary
b 30
Flow/return temperature differential too high
Check no air in system or boiler
Check adequate flow of water through boiler
b 33
Tank sensor short circuit
Check wiring
Disconnect terminals from tank sensor & confirm
short circuit using meter
Replace tank sensor
b 38
Tank sensor open circuit
If not fitted check parameter 35 settings
Check wiring
Disconnect terminals from tank sensor & confirm
open circuit using meter
Replace tank sensor
b 61
Air pressure switch closed (W80 only)
Check for blockages in air pressure switch
sensing pipes
Check air pressure switch & replace if necessary
b 65
Waiting for fan tacho signal at start up
Check fan wiring
If no tacho signal from fan, replace fan
Boiler Control Module Blocking Codes