41 EVomAX uSER IntERfACE - ADVAnCED oPERAtInG InStRuCtIonS ContInuED....
ENAblING VAlVE POWER OPEN/VAlVE POWER ClOSEd/SHUNT PUMP
The boiler default setting is the CH Pump output will only be On for a CH
Demand and the DHW Pump output will only be on for a DHW Demand.
This can be changed so that the CH Pump output controls the system pump
and the DHW Pump output operates a Valve (power open or power shut)
This can also be changed so that the CH Pump output controls a system
pump and the DHW Pump output controls a shunt pump
Press SELECT and then hold + and - down together for more than 5s, the
following screen will be displayed
Installer Mode
normal operation
Set Flow Temp’
Set DHW Temp’
Rotate the KNOB clockwise until the following screen is displayed
Installer Mode
Set Night Setback
dHW Pump/Valve
Set Booster
CH/DHW Priority
Press SELECT and the following screen will be displayed
DHW Pump/Valve
Pump
Valve Power Open
Press - for more
Press + and - to change to the required setting and then press ENTER
to store
Rotate the KNOB anti-clockwise until Normal Operation is highlighted
again and press SELECT to return to normal operation
continued . . . . . . . .
EnAbLInG nIGHt SEtbACk
Note- Night Setback is only operational if Outside Sensor has been connected
When Night Setback is enabled the boiler will run at the normal flow temp.
during CH Demand and reduced temperature when for no demand
Press SELECT and then hold + and - down together for more than 5s, the
following screen will be displayed
Installer Mode
normal operation
Set Flow Temp’
Set DHW Temp’
Rotate the KNOB clockwise until the following screen is displayed
Installer Mode
Set to 0-10V Input
Set night Setback
DHW Pump / Valve
Set Booster
Press SELECT and the following screen will be displayed
Set Night Setback
On
off
Press + and - to change to required setting and then press ENTER to store
Rotate the KNOB anti-clockwise until Normal Operation is highlighted
again and press SELECT to return to normal operation
Installer Mode
normal operation
Set Flow Temp’
Set DHW Temp’
Note- Booster Function is only operational if Outside Sensor has
been connected
If Booster function is enabled and CH Demand is ongoing for more
than 10 minutes then the Flow Temp. target is increased by 10°C
When the Burner switches off the temperature is reset
Press SELECT and then hold + and - down together for more than
5s, the following screen will be displayed
Rotate the KNOB clockwise until the following screen is displayed
Installer Mode
DHW Pump / Valve
Set booster
CH/DHW Priority
Set Max Flow Temp’
Press SELECT and the following screen will be displayed
Set Booster
On
off
Press + and - to change to required setting then press ENTER to store
Rotate the KNOB anti-clockwise until Normal Operation is highlighted
again and press SELECT to return to normal operation
CHANGING CH / dHW PRIORITy
Installer Mode
normal operation
Set Flow Temp’
Set DHW Temp’
The boiler default setting is DHW always has priority ahead of CH
It is possible to change this so CH always has priority ahead of DHW
or the boiler alternates between DHW and CH every 10 mins
Press SELECT and then hold + and - down together for more than 5s,
the following screen will be displayed
Rotate the KNOB clockwise until the following screen is displayed
Installer Mode
Set Booster
CH/dHW Priority
Set Max Flow Temp’
Set Min Flow Temp’
Press SELECT and the following screen will be displayed
CH/DHW Priority
Priority = DHW
Priority = CH
Priority = Equal
Press + and - to change to the required setting and then press
ENTER to store
Rotate the KNOB clockwise until Normal Operation is highlighted
again and press SELECT to return to normal operation