14
EVOMAX
-
Installation & Servicing
InStALLAtIon
16 oPEn fLuE kItS
Contents
158662 / 158663
• Boiler a screws (x6)
• Air inlet grille
158769 / 158770
• Terminal
note
: See Frame 18 for elbow equivalent lengths.
RF 2501
14 VERtICAL Roof fLuE kIt
Contents
• Boiler a screws (x6)
• Terminal
• Locking Collar
• Finishing plates (x2)
• Bracket
RF 2498
note
: See Frame 18 for elbow equivalent lengths.
15 VERtICAL Roof fLuE kIt -
Contents
• Boiler a screws (x6)
• Increaser
• Terminal
• Locking Collars (x2)
• Finishing plates (x2)
• Bracket
RF 2499
note
: See Frame 18 for elbow equivalent lengths.
FLUE OUTLET
Evomax vertical concentric flue application ~ maximum lengths and pressure differentials
Model
30/30P
40/40P
60/60P
80/80P
100
120
150
Max flue length (m)
42
42
7.5
12
20
17.6
7.5
Max flue press diff (Pa)
140
200
117
260
220
288
290
Flue Size
80 / 125
100 / 150
Vertical flue kit No
158654
158656
Evomax 60 & 80 vertical concentric flues of
longer length
Model
60/60P
80/80P
Max flue length (m)
30
35
Max flue press diff (Pa)
133
250
Flue Size
100 / 150
Vertical flue kit No
158655
Evomax open flue application ~ maximum lengths and pressure differentials
Model
30/30P
40/40P
60/60P
80/80P
100
120
150
Max flue length (m)
65
70
25
22
20
49
32
Max flue press diff (Pa)
140
225
150
312
220
365
430
Flue Size
80/125
100/150
Open flue kit No
158769
158770
206210-3.indd 14