2
EVOMAX
-
Installation & Servicing
GEnERAL
note
.
Natural gas consumption is calculated using a calorific value of
37.8MJ/m
3
(1038Btu/ft
3
) gross or 34 MJ/m
3
(910 Btu/ft
3
) nett at
15
o
C and 1013.25 mbar.
a
. For l/s divide the gross heat input (kW) by the gross C.V. of the
gas (MJ/m
3
)
b. For ft/h
3
divide the gross heat input (Btu/h) by the gross C.V. of
the gas (Btu/ft
3
).
c. For m
3
/h multiply l/s by 3.6.
Propane gas consumption is calculated using a calorific value of
95.7 MJ/m
3
(2500 Btu/ft.
3
) gross or 88.0 MJ/m
3
(2300 Btu/ft.
3
) net
at 15
o
C and 1013.25 mbar.
To obtain the fuel consumption in liquid form divide the above
figures by 270.
* The value is used in the UK Government’s Standard Assessment
Procedure (SAP) for energy ratings of dwellings. The test data from which
it has been calculated have been certified by a notified body.
table 2 General Data
HEALtH & SAfEty DoCumEnt no. 635
the electricity at work regulations, 1989
. The manufacturer’s
notes must NOT be taken, in any way, as overriding statutory
obligations.
ImPoRtAnt
. These appliances are CE certified for safety
and performance. It is, therefore, important that no external
control devices, e.g. flue dampers, economisers etc., are
directly connected to these appliances unless covered by
these Installation and Servicing Instructions or as otherwise
recommended by
Ideal Stelrad Group
in writing. If in doubt
please enquire.
Any direct connection of a control device not approved by
Ideal Stelrad Group
could invalidate the certification and the
normal appliance warranty. It could also infringe the Gas Safety
Regulations and the above regulations.
Evomax model
30
30P
40
40P
60
60P
80
80P
100
120
150
Boiler Output
(non-
condensing)
Mean 70
°
C
Max
kW
30
30
40
40
60
60
80
80
100
120
150
Btu/hr
102350
102350
136500
136500
204750
204750
273000
273000
341200
409450
511800
Min
kW
6
6
8
8
12
12
16
16
20
24
30
Btu/hr
20450
20450
27300
27300
40950
40950
54600
54600
68250
81900
102350
Boiler Output
(condensing)
Mean 40
°
C
Max
kW
31.54
30.9
42.0
41.2
63.5
62.1
84.4
82.6
103.9
124.7
158.0
Btu/hr
107600
105450
143300
140600
216650
211900
288000
281850
357360
428900
539100
Min
kW
6.5
6.4
8.5
8.3
12.6
12.4
17.3
17
21.6
26.0
32.5
Btu/hr
22200
21850
29000
28300
43000
42300
59050
58000
81620
98250
110800
Boiler Input
Max Rate
Nett
kW
30.4
30.4
40.5
40.5
60.8
60.8
82.0
82
102.4
122.9
153.7
Btu/hr
103700
103700
138250
138250
207400
207400
279650
279650
349550
419500
524350
Gross
kW
33.7
33
44.9
44
67.4
66
90.9
88.9
113.6
136.4
170.5
Btu/hr
115000
112600
153350
150150
230050
225200
310200
303350
387750
465300
581600
Boiler Input
Min Rate
Nett
kW
6.1
6.1
8.1
8.1
12.2
12.2
16.4
16.4
20.5
24.6
30.7
Btu/hr
20750
20750
27650
27650
41500
41500
55950
55950
69900
83900
104900
Gross
kW
6.7
6.6
9.0
8.8
13.5
13.2
18.2
17.8
22.7
27.3
34.1
Btu/hr
23000
22500
30650
30050
46000
45050
62050
60750
77550
93050
116300
Gas Rate
Max Rate
m
3
/hr
3.2
1.26
4.3
1.69
6.4
2.53
8.7
3.41
10.8
13.0
16.2
ft
3
/hr
113.4
44.7
151.2
59.6
226.9
89.3
305.9
120.3
382.4
458.9
573.6
Flue Gas
Flow Rate
Max Rate
m
3
/hr
47.6
46.5
63.4
62.1
95.1
93.1
128.3
125.4
160.3
192.5
240.7
ft
3
/hr
1680
1644
2238
2194
3360
3287
4531
4430
5662
6799
8499
CO
2
(±0.5%)
Max Rate
%
9.7
11.4
9.7
11.4
9.7
11.4
9.7
11.4
9.7
9.7
9.7
Min Rate
%
8.7
10.2
8.7
10.2
8.7
10.2
8.7
10.2
8.7
8.7
8.7
NO
x
weighted
mg/kWh
31.0
79
39.1
80
32.3
58
39.8
76
39.6
38.8
38.1
ppm
17.6
45
22.2
45
18.3
33
22.9
43
22.5
22.0
21.6
Efficiency
Seasonal
%
96.7
97.2
96.2
96.7
96.4
96.9
97.2
97.7
96.7
96.6
96.7
*SEDBUK 2009
%
89.6
90.6
89.3
90.3
89.4
90.5
n/a
n/a
n/a
n/a
n/a
Evomax model
30
30P
40
40P
60
60P
80
80P
100
120
150
Gas Supply
2H – G20 – 20mbar / 3P - G31 - 37mbar
Gas Supply Connection
G
3
/
4
Flow Connection
G1
1
/
4
Return Connection
G1
1
/
4
Max Pressure (sealed sys) Bar (psi)
4.0 (58)
Maximum Static Head
m
40.7
Electricity Supply
230V - 50Hz
Fuse Rating
A
4.0
Power Consumption
W
126
207
131
265
370
403
400
IP Rating
IP20
Nominal flue dia - Concent.
80/125
100/150
Condensate Drain
25
Water Content
L
3.0
5.0
7.0
9.2
Dry Weight
Kg
49
60.30
75.70
89.75
table 1 Performance Data (natural Gas)
206210-3.indd 2
09/06/2011 13:34:03