26
CONTROL
9.0 CONSUMPTION REPORTS
Energy consumption is calculated using the data you
provided during Luminaire Controller configuration. Click
CONSUMPTION from the main AudacyControls.com
menu. There are multiple options available to utilize the
consumption data.
9.2 BY AREA
This report allows you to view a historical record of
consumption that can be broken down by location over a
specific date range.
Note: You must click UPDATE to refresh the graph after the
desired date range is selected
9.3 EXPORTING CONSUMPTION DATA
Click EXPORT CSV on the left hand side of the screen to download a CSV file for the selected Date Range containing the
Date, Room Name, and associated Watt Hours.
9.0 CONSUMPTION REPORTS
9.1 OVER TIME
This report allows you to view a historical record of
consumption that can be broken down to a specific date
range, room and time period.
Note: You must click UPDATE to refresh the graph after the
desired data is selected.
SOURCE
– Choose to view the consumption of all rooms or select
a specific room to view.
DATE RANGE
– Select a start and an end date to view the
consumption data between those dates.
BY
– Select the time period each data point on the graph will
represent: Day, Week or Month.
Note: Power Consumption is a calculated value based on the duration that the light fixtures are on. Other factors like dim levels
set and the values input for voltage, power factor and Ampere draw will affect calculations (see section 6.2.6). Fluorescent lamp
power consumption data uses a modified 0-10V dimming curve that reflects a typical non-linear characteristic. For typical LED
fixtures, a linear 0-10V dimming curve is used.
9.4 BUILDING AUTOMATION INTEGRATION
The Audacy
®
Wireless Controls system can be tied into a Building
Automation System if desired. The Gateway can interface with a
wide range of BAS protocols including BACnet
®
/IP, BACnet
®
/MSTP,
Modbus TCP, Metasys
®
N2, Modbus RTU and LonWorks
®
. For
specific requirements please call Audacy Customer Service at
800-273-9989 for assistance with integrating Audacy with your BAS.
The BAS controls lights at the room level. The following fields are
available to the BAS:
Room:
•
Occupancy Status (Read Only)
•
Vacancy Timeout (Read Only)
•
State (Read and Write)
•
Value 0-100: 0 = relay off, 1-100 = DIM level
•
Scene 1, 2, 3 or 4
•
Switch: Battery Voltage (Read Only)
•
State (Read and Write)
•
Value 0-100: 0 = relay off, 1-100 = DIM level
•
Occupancy Sensor: Battery Voltage (Read Only)
•
Light Sensor: Light Level and Battery Voltage
(Read Only)
Содержание Audacy Wireless Controls
Страница 1: ...1 OPERATIONS USER MANUAL NOVEMBER 2016 ...
Страница 5: ...5 INSTALL ...
Страница 17: ...17 CONFIGURE ...
Страница 20: ...20 CONTROL ...
Страница 27: ...27 APPENDIX ...
Страница 34: ...34 APPENDIX F LUMINAIRE CONTROLLER ONE LINE DRAWINGS ESCGRID 1000 PWM LUMINAIRE CONTROLLER ...
Страница 35: ...35 APPENDIX E LUMINAIRE CONTROLLER REQUIREMENTS ESCD 1000 LVDC LUMINAIRE CONTROLLER EXTERNAL MOUNT ...
Страница 36: ...36 APPENDIX F LUMINAIRE CONTROLLER WIRING DIAGRAMS SCC 1000 347V LUMINAIRE CONTROLLER AT FIXTURE ...
Страница 37: ...37 APPENDIX F LUMINAIRE CONTROLLER WIRING DIAGRAMS SCL 1000 LUMINAIRE CONTROLLER INTERNAL MOUNT AT FIXTURE ...
Страница 39: ...39 APPENDIX F LUMINAIRE CONTROLLER WIRING DIAGRAMS SCD 1000 LUMINAIRE CONTROLLER EXTERNAL MOUNT ON FIXTURE ...
Страница 40: ...40 APPENDIX F LUMINAIRE CONTROLLER WIRING DIAGRAMS SCD 1000 LUMINAIRE CONTROLLER EXTERNAL MOUNT MULTI FIXTURE ...
Страница 42: ...42 APPENDIX G SENSOR COVERAGE PATTERNS WALL MOUNT MODEL VSW 1300 G SENSOR COVERAGE PATTERNS ...
Страница 43: ...43 APPENDIX F LUMINAIRE CONTROLLER ONE LINE DRAWINGS CEILING MOUNT MODEL VSC 1300 ...
Страница 47: ...47 APPENDIX Duplicate as needed ROOM LOCATION DEVICE TYPE SERIAL ...