18
CONFIGURE
7.0 SYSTEM CONFIGURATION
5. In certain situations, it may be necessary to
enable the repeater function on selected Luminaire
Controllers to extend the wireless range of your
Audacy Wireless Controls system. In order to do so,
perform the following steps.
a. Select room in which the desired Luminaire
Controller will be enabled as repeater.
b. Select the Luminaire Controller.
Once all the devices are assigned to a room, the control devices such as switches, light sensors* and motion sensors need
to be associated with the Luminaire Controllers they will control.
7.1 ASSOCIATING DEVICES
7.0 SYSTEM CONFIGURATION
1. Click SETUP.
2. Select the desired room in which devices need to be
associated.
3. For each control device in the room, place a
checkmark next to each Luminaire Controller you
want that device to control (for example in the image
above, “Elm Handheld” is configured to control
Fixture Zone-9b-1 and Zone-9b-2).
4. Click SAVE.
c. Click to access settings and enable repeater.
NOTE: It is not recommended to enable the repeater function
on all Luminaire Controllers. Enabling more repeaters
than necessary may have a negative impact on system
performance. A maximum of 5 repeaters may be enabled per
Gateway.
*NOTE: Once a minute, the Light Sensor will send a light level reading to the Gateway. The Gateway will process the reading and if it is within the acceptable window of upper and
lower light levels as indicated by the slider setting on the Audacy Interface, no change will happen. Once light in the space, due to daylighting, moves above or below these set points
the luminaire controller in the space will adjust the lights accordingly. If current light level is above the daylight upper limit, then the controller will reduce the lighting in the space, and
when the light level is below the daylight lower limit, the controller will increase the lighting in the space. The lighting will adjust in 5% increments (or 20 steps from 100% to 0%) at
each minute while the light level is outside the desired lighting band.
Содержание Audacy Wireless Controls
Страница 1: ...1 OPERATIONS USER MANUAL NOVEMBER 2016 ...
Страница 5: ...5 INSTALL ...
Страница 17: ...17 CONFIGURE ...
Страница 20: ...20 CONTROL ...
Страница 27: ...27 APPENDIX ...
Страница 34: ...34 APPENDIX F LUMINAIRE CONTROLLER ONE LINE DRAWINGS ESCGRID 1000 PWM LUMINAIRE CONTROLLER ...
Страница 35: ...35 APPENDIX E LUMINAIRE CONTROLLER REQUIREMENTS ESCD 1000 LVDC LUMINAIRE CONTROLLER EXTERNAL MOUNT ...
Страница 36: ...36 APPENDIX F LUMINAIRE CONTROLLER WIRING DIAGRAMS SCC 1000 347V LUMINAIRE CONTROLLER AT FIXTURE ...
Страница 37: ...37 APPENDIX F LUMINAIRE CONTROLLER WIRING DIAGRAMS SCL 1000 LUMINAIRE CONTROLLER INTERNAL MOUNT AT FIXTURE ...
Страница 39: ...39 APPENDIX F LUMINAIRE CONTROLLER WIRING DIAGRAMS SCD 1000 LUMINAIRE CONTROLLER EXTERNAL MOUNT ON FIXTURE ...
Страница 40: ...40 APPENDIX F LUMINAIRE CONTROLLER WIRING DIAGRAMS SCD 1000 LUMINAIRE CONTROLLER EXTERNAL MOUNT MULTI FIXTURE ...
Страница 42: ...42 APPENDIX G SENSOR COVERAGE PATTERNS WALL MOUNT MODEL VSW 1300 G SENSOR COVERAGE PATTERNS ...
Страница 43: ...43 APPENDIX F LUMINAIRE CONTROLLER ONE LINE DRAWINGS CEILING MOUNT MODEL VSC 1300 ...
Страница 47: ...47 APPENDIX Duplicate as needed ROOM LOCATION DEVICE TYPE SERIAL ...