25
Installation and Servicing
FLUE OUTLET
Section 2 - Installation
2.15 REAR FLUE OUTLET KIT (55/80) ASSEMBLY - EXPLODED VIEW
2.16 TERMINAL WALL SEAL ASSEMBLY / POSITIONING
2.17 SETTING THE REAR FLUE LENGTH - WALL THICKNESS OF 115 MM TO 442 MM
1.
Rear flue (55/80)
2.
Plastic Connector
3.
Wall Mounting Plate
1
2
3
Ensure lip of wall seal is positioned
over step on plastic nose of flue terminal
(note, seal is cut away for clarity)
Step
205862-10137
Wall Seal Lip
Prior to fitting the flue, the rubber terminal wall seal provided
in the flue pack MUST be fitted to the flue terminal as shown
below.
Once the flue is installed it is
IMPORTANT that the rubber
terminal wall seal is pressed against the outside wall to
create an adequate seal between the flue and wall as
shown below.
205862-10072
Rubber
Terminal
Wall Seal
1. Measure and note wall thickness X.
2. Add 8 mm to dimension X and, measuring from the ring,
cut the outer tube only.
3. To ensure the tube is cut square, mark the flue all the
way around.
4. Cut the inner tube to a length 10 mm longer to aid
engagement, using the cutting aid provided.
Note
. If the stand-off frame is used, it is essential to add 45
mm to ‘X’ the measured wall thickness when marking the
flue (this will allow for the fitted frame)
Measure from
this
RING
3G9675
Wall Thickness X
1
2
3
Refer to Section
2.14