48
Installation and Servicing
Section 4 - Fault Finding
Section 4 - Fault Finding
FAUL
T FINDING
4.1 FAULT FINDING MAIN MENU
‘L 01’
Go to Section 4.2: Flow Temperature Overheat Lockout
‘L 02’
Go to Section 4.3: Ignition Lockout
‘L 0C’
5 Restarts within 15 minutes: Turnpower off & on
‘L 06’
Go to Section 4.4: False Flame Lockout
‘F 02’
Go to Section 4.5: Flame Loss
‘F 03’
Go to Section 4.6: Fan Fault
‘L 04’ or ‘F 04’
Go to Section 4.7: Flow Thermistor Fault
‘L 05’ or ‘F 05’
Go to Section 4.9: Return Thermistor Fault
‘F 06’
Go to Section 4.10: Outside Sensor Fault
‘F 07’
Low Mains Voltage: Contact Electricity Provider
‘F 09’
PCB Fault: Replace PCB
‘F 0A’
Go to Section 4.8: Flow/Return Reversed
‘F 0U’
Go to Section 4.14: Flow/Return Differential greater than 50°C
No CH, but HW OK
Go to Section 4.11
No HW, but CH OK
Go to Section 4.13
No Display
Go to Section 4.12
‘F 0t’
Room Thermostat Fault: Check Room Stat & connections
‘F 10’
Spark Generator Fault: Check wiring, if OK replace spark generator
‘F 0d’
Go to Section 4.6: No Water Flow
‘L 0d’
Go to Section 4.3: Ignition Lockout: Blocked Flue/Condensate