23
3.9.11
Menu – Cascade manager -
Settings - Hours run
The sequence changeover will occur after
the number of burner hours hav been
completed by the current lead boiler. It can
be set in multiples of 10 hours as shown
below. Select Done to confirm the change.
Hours run
100hours
Done
3.9.12
Menu – Cascade manager –
Settings - Timed
The sequence changeover will occur after
the Timed period has been completed. It can
be set in multiples of 1 day as shown below.
Select Done to confirm the change.
Hours run
7day(s)
Done
3.9.13
Menu – Cascade manager –
Settings - Ext. heat source sequence
The sequence order location for the External
heat source can be set. It can be set to be
always the first in the sequence order or the
last in the sequence order. Select Done to
confirm the change.
Ext. heat souce sequence
Always first
Done
Ext. heat souce sequence
Always last
Done