PRT-CTRL-SE
Protege SE Integrated System Controller
Installation Manual | June 2017
9
4
Connections
4.1
Protege SE Integrated System Controller Connection
The Protege
®
SE Integrated System
Controller shall be supplied by a
dedicated electrical power source rated
for a minimum 10Amp load and have a
dedicated circuit breaker. Do not use a
switch controlled breaker or switched
electrical point to supply electrical power.
CAUTION:
INCORRECT
WIRING MAY RESULT IN
DAMAGE TO THE UNIT
Protege System
RJ31X
REX
N.O Zone Contact
N.C Zone Contact
1K
1K
Door Contact
1K
1K
1K
1K
Bond Sense
N.C Zone Contact
1K
1K
REN
N.O Zone Contact
Nano Prox Reader
(Optional Extra)
+A
UX
-
Z1
COM
CO
M
Z2
Z3
Z4
N.C
Tamper
N.C Zone Contact
Value 2
Value 1
+A
UX
-
Z1
COM
CO
M
Z2
Z3
Z4
Shield
Red
Black
Green
White
Orange
Brown
Blue
Yellow
+
-
+
-
1k Resistors
1N4007
Diode
8 Ohm 30W
Siren or 1.1A
(Maximum)
+
-
1N4007
Diode
Electric
Locking Device
Relay
+
-
Lock
Power Supply
+
-
+
-
1k Resistors
1N4007
Diode
1.1A (Maximum)
Electric
Locking Device
1.1A (Maximum)
Electric
Locking Device
8 Ohm 30W
Siren or 1.1A
(Maximum)
Zone Options
The onboard readers ports use zone input 9 – 12 and
13 - 16 as door contact, REX, bond sense and REN
inputs respectively. Any of these inputs that are not
used as general purpose zone inputs. Please refer
to the Protege
®
SE Integrated System Controller
Installation Manual Section 5.5 Programming the
Onboard Reader.
Typical Zone Circuits
B1+
B1-
B2+
B2-
P3
P4
T+
T-
+
-
NO
CO
M
NC
1K5 OHM
LED
Programmable Outputs
PGMs 3/4
The PGM Outputs 3 (PGM3 CP001:03) and 4
(PGM CP001:4) are Open Collector Outputs and
switch to OV. The PGM’s can be used to activate
relays, sounders and lights.
Grey
Brown
Red
Green
+
-
Transformer:
16 to 16.5VAC
secondary
(via transformer)
Cold water
earth pipe
Tamper
Switch
Bracket
Gel Cell
Backup
Battery
(Min 7Ah)
NA
N+
N-
NB
Protege
®
SE Integrated System
Controller or module supplying
power to networked devices
AUX power from Module
or external power supply
Next modules
on network
NA
N+
N-
NB
+AUX-
Z13 COM
COM
Z14 Z15
Z16
White
Blue
Black
Red
Switches 1 & 2 - Operating Mode
Switch
Switch
Function
1
2
Power Up Boot Mode
OFF
OFF
Normal Operation*
ON
OFF
BOOT Loader
OFF
ON
BIOS Utility
ON
ON
Reserved Do Not Set
Switch 3 - IP Address Override
OFF
Normal Operation*
ON
IP will be set to 192.168.111.222
while this switch remains on
Switch 4 - Memory Default
OFF
Normal Operation*
ON
Factory Default
*Default Setting
LED Indicators
LED
Description
Status
Slow Flash
Controller operating normally
Fast Flash
Controller is in BIOS mode
Fault
ON
Controller is in BIOS mode
OFF
Controller operating normally
Slow Flash
update
Charge /
Test
Varying
Intensity
Battery is being charged, indicator’s intensity
shows charging current
ON
Battery test in progress
OFF
Battery is fully charged (if AC Indicator is ON)
AUX1 /
AUX2
ON
Auxiliary supply is normal
OFF
Auxiliary supply is in over current protection
AC
ON
Valid AC input provided
OFF
AC is disconnected or has failed
5V ISO
ON
Valid power supply provided
OFF
Power supply disconnected or is not powered
properly
LOCK1 /
LOCK2
BELL1 /
BELL2
ON
LOCK/BELL is ON
OFF
LOCK/BELL is OFF
2 Flashes
LOCK/BELL is ON, the circuit is in over current
protection
3 Flashes
LOCK/BELL is OFF, the circuit to the locking
device is cut, damaged, or tampered
Network
RX / TX
Fast Flash
Data packet transmitted/received
OFF
No data packet transmitted/received
Ethernet
Link
ON
Live Ethernet connection detected
OFF
No Ethernet connection detected
Fast Flash
Ethernet packet transmitted/received
Ethernet
100Mb
ON
Ethernet connection operates at 100Mb
OFF
Ethernet connection does not operate at
100Mb
R1 / R2
Data
Slow Flash
Data received in valid format
Fast Flash
Data received in invalid format
ONLINE
ON
Onboard modem off hook
OFF
Onboard modem not active
Wiring
EARTH GND WIRING: Minimum 14AWG solid copper wire.
ZONE WIRING: maximum distance of 300m (1000ft) from the Protege
®
SE Integrated System Controller when using 22 AWG.
AUX WIRING: Min 22AWG Max 16AWG. (Depends on length and Current
consumption). For wire/cable size, a maximum of 5% voltage drop at the
terminals of the powered device has to be observed.
ETHERNET WIRING: CAT5e / CAT6 max 100m (330 ft)
MODULE NETWORK WIRING: Recommended Belden 9842 or equivalent.
(24AWG twisted pair with characteristic impedance of 120ohm or CAT5e /
CAT6 are also supported for Data Transmission when using ground in the
same cable.
Do not use extra wires to power devices.)
max 900m (3000ft).
Modem Interface
Surge Protector
L-COM
HGLN-D1DT
Earth Ground Link connection
provided via metallic enclosure
Value 1
Value 2
Monitored Status
1K
1K
Open, Close, Tamper, Short
6K8
2K2
Open, Close, Tamper, Short
10K
10K
Open, Close, Tamper, Short
2K2
2K2
Open, Close, Tamper, Short
4K7
2K2
Open, Close, Tamper, Short
4K7
4K7
Open, Close, Tamper, Short
ULC-LA AC
Indicator*
Inline
5A 3AG
fuseholder*
*When installed with the power supply manufactured by Marcus (Model M4758CT), the Digital Security
Controls (DSC) Model ULC-LA power indicator light assembly (Installation Instruction No. 29001877 R0)
must be installed within a conduit knockout of the ICT Model CAB-LARGE-UL or Bosch Model D8108A
enclosure in order to provide green AC power on indication. The Littelfuse Part No. 150322 fuseholder
and Littelfuse Part No. 0312005 5A, 3AG fast-acting fuse must be installed in-line to the Models
PRT-CTRL-SE, PRT-ZX16-PCB and PRT-RDI2-PCB.
Servicing of the
CR2032 battery
must be done by a
trained technician.